Commercial power supply-inverter switch-over function (Pr. 135 to Pr. 139)

Pr. 135 "commercial power supply-inverter
switch-over sequence output terminal selection"
Pr. 136 "MC switch-over interlock time"
Pr. 137 "start waiting time"
Pr. 138 "commercial power supply-inverter
switch-over selection at alarm occurrence"
Pr. 139 "automatic inverter-commercial power
supply switch-over frequency"
The inverter contains a complicated sequence circuit for commercial power supply-inverter operation switch-
over. Hence, the magnetic contactors for switch-over can be interlocked easily by merely entering the start,
stop or automatic switch-over select signal.
Parameter
Factory Setting
Number
135
0
136
0.1 sec.
137
0.5 sec.
138
0
139
9999
( 1 ) Wiring example
Sink logic, Pr. 185 = 7, Pr. 186 = 6, Pr. 192 = 17, Pr. 193 = 18, Pr. 194 = 19
Inverter
NFB
MC1
R 〈L
U
1
S 〈L
V
2
T 〈L
W
3
R1 〈L
11
S1 〈L
21
SU
Inverter start
(forward rotation)
STF
IPF
Inverter-commercial
CS
power supply
MRS
OL
switch-over
Operation interlock
FU
*3
External thermal relay
OH
SE
Reset
RES
SD
10
Frequency setting signal
2
5
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Setting Range
Remarks
0, 1
0 to 100.0 sec.
0 to 100.0 sec.
0,1
9999: No automatic
0 to 60.0Hz, 9999
switch-over
MC2
Note:
This switch-over function is used in the external operation
R
mode. Always connect terminals R1, S1 (L
different power supply (power supply different from the one
×
for MC1) to ensure proper operation.
External
MC3
MC2 and MC3 must be mechanically interlocked.
thermal relay
R
IM
*1. Note the sequence output terminal capacities. The terminals used
depend on the Pr. 190 to Pr. 194 settings.
Output Terminal Capacity
Signal set in Pr. 190 to Pr. 195
Inverter's open collector outputs
*1
MC
1
(IPF, OL, FU)
*2
*1
MC3
MC
DC24V
2
FR-A5AR (option output)
*1
MC2
MC
3
*2. When connecting an AC power supply, connect the FR-A5AR option
and use the contact output.
When connecting a DC power supply, install the following protective
diode.
*3. The terminals used depend on the Pr. 180 to Pr. 186 settings.
IPF
OL
FU
DC
24V
SE
131
PARAMETERS
Related parameters
Pr. 11 "DC dynamic brake operation
time"
Pr. 17 "MRS input selection"
Pr. 57 "restart coasting time"
Pr. 58 "restart cushion time"
Pr. 180 to Pr. 186
(input terminal function selection)
Pr. 190 to Pr. 195
(output terminal function selection)
, L
) to a
11
21
Permissible Output Terminal Load
24VDC 0.1A
230VAC 0.3A
30VDC 0.3A