<Setting procedure>
(Example: Set point No. 1, forward rotation, 30Hz, 4 hours 30 minutes)
1) Read Pr. 201 value.
2) Enter "1" (forward rotation) in Pr. 201 and press the [SET] key ([WRITE] key when using the FR-PU04
parameter unit).
3) Enter 30 (30Hz) and press the [SET] key ([WRITE] key when using the FR-PU04 parameter unit). (Note 1)
4) Enter "4.30" and press the [SET] key ([WRITE] key when using the FR-PU04 parameter unit). (Note 2)
5) Press the [UP] key to move to the next parameter (Pr. 202), and press the [SET] key ([READ] key when
using the FR-PU04 parameter unit) to display the current setting. Hereafter, press the [UP] key to advance
the parameter one by one.
Note 1: To make a stop, write "0" in the rotation direction and frequency. Set "9999" for no
setting.
Note 2: An error will result if 4.80 is entered (59 minutes or 59 seconds is exceeded).
·
Assuming that operation has been programmed as indicated in the following table, the operation
pattern is as shown in the figure below:
No.
Operation
Forward rotation, 20Hz, 1 hour 0
1
minutes
2
Stop, 3 hours 0 minutes
Reverse rotation, 30Hz, 4 hours 0
3
minutes
Forward rotation, 10Hz, 6 hours 0
4
minutes
Forward rotation, 35Hz, 7 hours 30
5
minutes
6
Stop, 9 hours 0 minutes
<Operation pattern>
2
Set point 1
Forward
20Hz
rotation
0
1
3
(4) Input signals
Name
Group signal
RH (group 1)
Used
RM (group 2)
programmed operation.
RL (group 3)
Timer reset signal (STR)
Input to zero the reference time of day.
Programmed operation start
Input to start programmed operation.
signal (STF)
(5) Output signals
Name
Output on completion of the operation of
Time-out signal (SU)
the selected group and cleared on timer
reset.
Output during running of corresponding
Group select signals
group's program and cleared on timer
(FU, OL, IPF)
reset.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Parameter Setting
Pr. 201 = 1, 20, 1:00
Pr. 202 = 0, 0, 3:00
Pr. 203 = 2, 30, 4:00
Pr. 204 = 1, 10, 6:00
Pr. 205 = 1, 35, 7:30
Pr. 206 = 0, 0, 9:00
3
4
5
6
35Hz
10Hz
4
6
7:30
9
Time of day
Description
to
select
the
group
for
Description
149
PARAMETERS
Signal Level
Remarks
May also be driven by
Photocoupler
transistor. When ic = 10mA,
isolated
Vec<0.5V should be satisfied.
Signal Level
Remarks
Permissible load
Open collector
24VDC, 0.1A
output (isolated)
Only when Pr. 76 = 3