4 - Operations
SECOND GROUP
Soft-start
# s t. O p
control output
value
Value of the control output during
the Soft-start activation time.
Soft-start
# s t. t M
activation time
Time duration (starting from the
power on) of the Soft-start func-
tion.
OP
100%
# S t. O P
Soft-start
# S t. t M
Power on
Output
# S A. O P
Safety Value
Output Value in case of input
anomaly
32
Controller
# A ddr
address
the address range is from 1 to 247
and must be unique for each con-
troller on the communication bus
to the supervisor.
Off
When set to
not communicating
Time

HEAT COOL CONTROL

By a sole PID control algorithm, the
controller handles two different out-
puts, one of these performs the
Heat action, the other one the Cool
action.
It is possible to overlap the out-
the controller is
puts.
The dead band parameter
is the zone where it is possible to
separate or overlap the Heat and
Cool actions.
The Cool action can be adjusted
using the relative cool gain para-
meter
To limit the Heat and Cool outputs
the parameters
can be used.
When there is an overlap, the dis-
played output
algebric sum of the Heat and Cool
outputs.
# d . b nd
# r . C . G a
.
# 0 p. H
# 0 p. H C
and
# OUt
shows the
,