Configuration Coding - ascon M3 Series User Manual

Table of Contents

Advertisement

3 - Product coding
3.2

CONFIGURATION CODING

The configuration code consists of
4 digits that identify the operat-
ing characteristic of the controller,
as chosen by the user.
Section 4.6 at page 35 reports the
instructions how to set a new con-
figuration code.
I L M N
2002
Conf
The configuration code can be dis-
played on the front panel, follow-
ing the instructions at page 21 sec-
tion 4.2.2.
18
Input type and range
TR Pt100 IEC751
TR Pt100 IEC751
TC L Fe-Const DIN43710
TC J Fe-Cu45% Ni IEC584
TC T Cu-CuNi
TC K Cromel -Alumel IEC584
TC S Pt10%Rh-Pt IEC584
DC input 0...50 mV, linear
DC input 10...50 mV, linear
Custom input and range [1]
Note
[1] For instance, other thermocouples types, ∆T (with 2 PT 100), custom lineari-
sation etc.
Control mode
Output configuration
Control OP1 / alarm AL2 on OP2
PID
Control OP2 / alarm AL2 on OP1
Control OP1 / alarm AL2 on OP2
On - Off
Control OP2 / alarm AL2 on OP1
Control OP1- OP3 / alarm AL2 on OP2
Heat/Cool
Control OP1- OP2 / alarm AL2 on OP3
action
Control OP2- OP3 / alarm AL2 on OP1
Control action type
Reverse (single action)
Direct (single action)
-99.9...300.0 °C
-99.9...572.0 °F
-200...600 °C
-328...1112 °F
0...600 °C
32...1112 °F
0...600 °C
32...1112 °F
-200 ...400 °C
-328...752 °F
0...1200 °C
32...2192 °F
0...1600 °C
32...2912 °F
Engineering units
Engineering units
Linear Cool (Heat/Cool double action)
On-Off Cool (Heat/Cool double action)
I
0
1
2
3
4
5
6
7
8
9
L
0
1
2
3
6
7
8
M
0
1