4-3-17 Gas leakage error
1. Inspection items
1) Is refrigerant filled?
2) Is the indoor EVA sensor connected properly?
2. Inspection order
Restart after turning off the power
Did error occur?
Is resistance value
of the different Compressor phases (U V,
V W, W U) less than 2Ω?
Is the service valve open completely?
Is the indoor EVA sensor connected properly?
Is refrigerant filled?
Replace the outdoor unit's PCB
4-30
Yes
Yes
Yes
Yes
Yes
No
Terminate the service
No
Replace the compressor
No
No
Reconnect the sensor connector
No
Open valves
ace th