HP StorageWorks XP10000 Disk Array Site Prep Manual page 39

Hide thumbs Also See for StorageWorks XP10000 Disk Array:
Table of Contents

Advertisement

Primary and second rack clearance notes and floor loading
The following explanatory notes apply to the preceding floor clearance drawings for the
primary and second rack.
*1: Clearance (a+b) depends on the floor load rating and clearance "c". Required
clearances for various floor load ratings are shown below.
*2: Clearance between racks must be at least 10 mm. If the kickplate is installed after
rack placement, allow 100 mm.
Floorload
rating
(kg/mm2)
500
450
400
350
300
Additional primary and second rack floor loading and clearance notes:
Decide actual clearances in consultation with the construction specialist
responsible for installation. They may vary depending on the size and layout of
the system and building conditions.
When multiple disk arrays are arranged in a row, base your clearance values on
the requirements of the largest disk array.
Generally, clearances ("c") should be as large as allowable.
Required clearance (a + b) mm
c = 0
c = 200
100
0.00
300
200
600
400
1000
800
1600
1300
HP StorageWorks XP10000 Disk Array Site Prep Guide
Clearance (c) mm
c = 400
c = 600
0.00
0.00
300
600
1100
c = 1000
0.00
0.00
0.00
0.00
200
0.00
500
200
900
600
39