Troubleshooting
Checking and acknowledging faults
Displayed
Con-
fault code
st.
F8
X
F9
X
FA
X
Fd
X
FE
X
84
Weat-
System
Cause
her-
character-
com-
istics
p.
X
Burner in
Fuel valve
fault state
closes too late
X
Burner in
Fan speed too
fault state
low at burner
start
X
Burner in
Fan stop not
fault state
achieved
X
Burner
Burner control
blocked
unit fault
X
Burner
Strong inter-
blocked
ference (EMC)
field nearby;
alternatively
boiler coding
card or main
PCB faulty
(cont.)
Remedy
Check gas combi-
nation valve. Check
both control paths.
Press E.
Check the fan,
check the fan
cables and supply,
check the fan con-
trol.
Press E.
Check the fan,
check the fan
cables, check the
fan control.
Press E.
Check the ignition
electrodes and
leads. Check
whether a strong
interference (EMC)
field exists near the
equipment.
Press E.
If the fault is not
removed, replace
the control unit.
Remove EMC inter-
ference. If the
equipment will not
restart, check the
boiler coding card
and replace, or
replace the control
unit.