Checking the burner gauze assembly

Replace the burner gauze assembly if
the wire mesh is damaged.
1. Remove electrodes A.
2. Release the six Torx screws B
and remove the burner gauze
assembly C.
3. Remove the old gauze assembly
gasket D.
Initial start-up, inspection, maintenance
(cont.)
4. Insert a new burner gauze assem-
bly with a new gasket, and secure
with six Torx screws.
Note
Torque: 3.5 Nm