Viessmann VITODENS 300 Service Instructions Manual page 82

6.6 to 35.0 kw gas fired wall mounted condensing boiler natural gas and lpg version
Hide thumbs Also See for VITODENS 300:
Table of Contents

Advertisement

Troubleshooting
Checking and acknowledging faults
Displayed
Con-
fault code
st.
CF
dA
db
dd
dE
E4
X
E5
X
E6
X
82
Weat-
System
Cause
her-
character-
com-
istics
p.
X
Control
Communica-
mode
tions fault -
LON commu-
nication mod-
ule
X
Control
Room tem-
mode with-
perature sen-
out room
sor heating
influence
circuit A1
shorted out
X
Control
Heating circuit
mode with-
M2 room tem-
out room
perature sen-
influence
sor shorted
out
X
Control
Room tem-
mode with-
perature sen-
out room
sor heating
influence
circuit A1 lead
break
X
Control
Heating circuit
mode with-
M2 room tem-
out room
perature sen-
influence
sor lead break
X
Burner
Fault - supply
blocked
voltage
X
Burner
Internal fault
blocked
X
Burner in
Flue gas/air
fault state
supply system
blocked
(cont.)
Remedy
Replace the LON
communication
module
Check the room
temperature sensor
for heating circuit
A1
Check the room
temperature sensor
for heating circuit
M2
Check the room
temperature sensor
for heating circuit
A1
Check the room
temperature sensor
for heating circuit
M2
Replace control unit
Check the ionisa-
tion electrode and
leads. Check flue
gas system for
soundness.
Press E.
Check the flue gas/
air supply system.
Check the differen-
tial pressure sen-
sor.
Press E.