Generator Ac Connection System - Briggs & Stratton Standby Generator Systems Installation & Start-Up Manual

Liquid-cooled generator system
Table of Contents

Advertisement

Generator AC Connection System

A single-phase, three-wire AC connection system is used
in the generator. The stator assembly consists of a pair
of stationary windings with two leads brought out of each
winding. The junction of leads 22 and 33 forms the neutral
lead, as shown schematically and as wiring diagram. A
complete schematic and wiring diagram can be found later in
this manual.
Neutral is not bonded to ground at generator.
22
33
Circuit
Breaker
44
11
Neutral
44
Circuit
N
Breaker
Neutral
Line 1
To Transfer Switch
10 A
240 VAC
24
Neutral
120 V
120 V
240 V
Ground
11
G
Line 2
Ground
10 A
NOTICE Prior to making connections, verify phase rotation
of utility power.
When making connections, obey wire type and torque
specifications shown on the circuit breaker and
neutral/ground connector.
BRIGGSandSTRATTON.COM