Pipe Checking Operation (Auto Addressing Mode)
Automated checking of pipe connection (Auto addressing option)
Turn on the outdoor unit and wait for one minute.
During these 60 seconds, the left dispaly DIS01 will show sequentially
00-01-02-03-...15-00.
E199 is showed on the display PCB of outdoor unit.
- It means you didn't do "Pipe check operation"
Push [K1] button on the display PCB of outdoor unit once,
then begins to start "Pipe check operation" with displaying as below.
Display
Time duration
 Expected time of 4 indoor units installation.
[DIS02] shows the indoor unit under searching
It could take more time depending on the indoor and outdoor temperature.
After completeing pipe check operation, it shows "
The left display DIS01 will show sequentially the following message:
00 - Estabilished communication with indoor unit "A";
01 - Estabilished communication with indoor unit "B";
02 - Estabilished communication with indoor unit "C";
03 - Estabilished communication with indoor unit "D";
00 - Estabilished communication with indoor unit "A"...
Function of Step 3
Mode
Auto Addressing
Manual Addressing
 If the auto addressing does not work according to the indoor unit capacity,
model or installation condition, apply the manual addressing.
When SW01 set "0" on Auto address mode, it means you install the maximum
number of indoor unit.
1) Installation ID Unit Number= MAX Installation ID Unit Number of OD Unit.
Don't need set SW01.
2) Installation ID Unit Number< MAX Installation ID Unit Number of OD Unit.
Pls set SW01 as the number of which you install the indoor unit.
On Manual address mode,you must set SW01 as the number of which you install
the indoor unit.
08'FJM_OUTDOOR_28896A_IM_E.indd 31
Button [Κ1] 1 times
DIS 01
[DIS 01] is flickering on the setting time.
Outdoor Temperature
0°C or more
(Cool mode)
5min ~ 10 min
20min ~ 50 min
Function
Checking the connection & addressing
Checking the connection only
DIS 02
Less than0°C
(Heat mode)
" on the display PCB.
COMPLETING THE INSTALLATION
31
E-
2007-12-12 14:28:56