Samsung MH040FXA2B Installation Manual page 17

Free joint multi & multi-split type room air conditioner
Table of Contents

Advertisement

MH070FXA4B / MH080FXA4B
A-unit
1(L) 2(N)
F1
F2
1 2
F1 F2
Earth
terminal
C
1 2
F1 F2
Earth
terminal
1(L) 2(N) 1(L) 2(N)
A
B
Power cable to indoor units
Cable Type: A
Cable Type: B
Cable Type: C
The specification for cables :
Main Power Supply Cable Indoor Power Supply Cable
Model
Specication
MH040FX*A2B
MH050FX*A2B
MH18VF1X
3G, 2.5mm 2 or
MH19VF1X
more,
MH060FX*A3B
H07RN-F
MH070FX*A4B
MH080FX*A4B
 Connect the power cable to the auxiliary circuit breaker.
If every pole fails to connect to the power supply, it must be
incorporated in a wire with a contact opening of ≥3mm.
08'FJM_OUTDOOR_28896A_IM_E.indd 17
B-unit
Indoor unit
1(L) 2(N)
F1
F2
Assembly cable
1 2
F1 F2
Earth
terminal
B
C
1
2
F1 F2
Earth
terminal
Outdoor unit
1(L) 2(N) 1(L) 2(N)
L
C
D
1
A
Type
Specication
Type
3G, 1.0mm 2 or
more,
H07RN-F
C-unit
1(L) 2(N)
F1
F2
1 2
F1 F2
Earth
terminal
B
C
1 2
F1 F2
Earth
terminal
Main Power
F1 F2 F1 F2
N
supply cable
2
Earth
terminal
Communication Cable
FUSE
Specication
Type
Frame : 30A
20A
Trip : 20A
2G, 0.75mm 2 or
more,
Frame : 30A
H07RN-F
20A
Trip : 25A
Frame : 30A
30A
Trip : 30A
INSTALLING THE OUTDOOR UNIT
D-unit
1(L) 2(N)
F1
F2
1 2
F1 F2
Earth
terminal
B
C
1
2
F1 F2
Earth
terminal
F1 F2 F1 F2
A
B
C
D
Communication cable
to indoor units
Type GL
MCCB
20A
25A
30A
17
E-
2007-12-12 14:28:22