Hitachi SJ7002 Series Instruction Manual page 144

Sj7002 series
Hide thumbs Also See for SJ7002 Series:
Table of Contents

Advertisement

Serial
Communications
Func.
Code
C071
Communication speed
selection
C072
Node allocation
Set the address of the inverter on the network
C073
Communication data length
selection
C074
Communication parity
selection
C075
Communication stop bit
selection
C076
Action upon communication
error selection
C077
Communication timeout before trip
C078
Communication wait time
Time the inverter waits after receiving a message before it transmits
C079
Communication protocol
select
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: info@clrwtr.com
The following table configures the communications port of the SJ700
up to thirty-two devices on the serial communications network. The inverters are slaves and the
computer or digital operator is the master. Thus, all inverters on the serial connection must use
the same baud rate, data length, parity, and stop bits. However, each device on the serial
network must have a unique node address. See
information.
Keypad
Name/
Description
SRW
TEST
2400bps
4800bps
9600bps
19200bps
7BIT
8BIT
NO
EVN
ODD
1BIT
2BIT
TRP
DSTP
NEG
FRS
DTP
ASCII
Modbus
"Serial Communications" on page B–1
Range and Settings
OPE
02
Test
03
2400 (bps)
04
4800 (bps)
05
9600 (bps)
06
19200 (bps)
1. to 32. (node)
07
7-bit data
08
8-bit data
00
No parity
0 1
Even parity
02
Odd parity
0 1
1 Stop bit
02
2 Stop bits
00
Trip
0 1
Trip after deceleration and stop
02
No action (ignore errors)
03
Free-run stop
04
Decelerate and stop
0.00 to 99.99 (seconds)
0.0 to 1000 (milliseconds)
00
ASCII
0 1
ModBus RTU
3–61
SJ700
Inverter
2
inverter. You can have
2
for more
Defaults
Run
Mode
xFE2
xFU2
xFF2
Edit
(EU)
(USA)
(Jpn)
Lo Hi
✘ ✔
04
04
04
✘ ✔
1.
1.
1.
✘ ✔
07
07
07
✘ ✔
00
00
00
✘ ✔
1
1
1
✘ ✔
02
02
02
✘ ✔
0.00
0.00
0.00
✘ ✔
0.
0.
0.
✘ ✔
00
00
00