Termination Locations; Vent Termination Minimum Clearances - Heat & Glo SOHO24B Owner's Manual

Hide thumbs Also See for SOHO24B:
Table of Contents

Advertisement

4 4

Termination Locations

A. Vent Termination Minimum Clearances
WARNING
Fire Risk.
Explosion Risk.
Maintain vent clearance to combustibles as
specifi ed.
• Do not pack air space with insulation or other
materials.
Failure to keep insulation or other materials
away from vent pipe may cause fi re.
Measure vertical clearances from this surface.
Measure horizontal clearances from this surface.
(See Figure 4.4 for specifi c clearances)
Figure 4.1
Figure 4.2 specifi es minimum vent heights for various
pitched roofs.
Heat & Glo • Soho24B • 2137-900 Rev. E • 11/07
2 FT.
20 INCHES MIN.
MIN.
LOWEST
DISCHARGE
OPENING
GAS DIRECT VENT
TERMINATION CAP
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
Roof Pitch
Flat to 6/12...........................................................1.0*
Over 6/12 to 7/12 .................................................1.25*
Over 7/12 to 8/12 .................................................1.5*
Over 8/12 to 9/12 .................................................2.0*
Over 9/12 to 10/12 ...............................................2.5
Over 10/12 to 11/12 .............................................3.25
Over 11/12 to 12/12 .............................................4.0
Over 12/12 to 14/12 .............................................5.0
Over 14/12 to 16/12 .............................................6.0
Over 16/12 to 18/12 .............................................7.0
Over 18/12 to 20/12 .............................................7.5
Over 20/12 to 21/12 .............................................8.0
* 3 foot minimum in snow regions
Figure 4.2 Minimum height from roof to lowest discharge
opening
GAS, WOOD OR FUEL
OIL TERMINATION
GAS
TERMINATION
C
A
Gas
Wood & Fuel Oil
Termination
Termination
A
6 in.
20 in. min.
B
20 in.
24 in. min.
C
18 in.
18 in.
Figure 4.3 Multiple Vertical Termination
HORIZONTAL
OVERHANG
VERTICAL
WALL
X
12
ROOF PITCH
IS X/ 12
H (Min.) Ft.
B
Comments
Horizontal distance between terminations
Distance to perpendicular wall
Vertical distance between terminations
9