PUSH-TO-OPEN LIMIT SETTING

PUSH-TO-OPEN LIMIT SETTING
(Open Gate to Outside)
Single Gate Installations
Step 1
Make sure the gate is in the fully closed position.
Ensure power switch is in the ON position.
Step 2
Verify Block 2, DIP Switch #1 is in OFF position and Block 2,
DIP switch 2 is in the ON position.
Press the cycle button on circuit board and the gate will
begin to open. Stop the gate using the cycle button when
the desired limit has been reached.
Step 3
Press and hold the "SET LIMIT" button until one audible
beep is heard to acquire the open limit setting. The STATUS
light will turn on immediately upon pressing the SET LIMIT
button. The STATUS light will turn off and an audible beep
will verify the open limit is now set.
Step 4
Press cycle button on circuit board to return the gate to the
fully closed position.
Step 5
Again, using the cycle button open the gate to verify it
meets the desired location. If the gate did NOT reach the
desired open limit, proceed to step 6.
Step 6
CLEARING THE OPEN LIMIT SETTING:
a) Return the gate to the fully closed position.
b) Press and hold the SET LIMIT button until two audible
beeps are heard.
c) Two audible beeps will verify the open limit setting is
now cleared.
Repeat steps 1 – 5 to program the gates "open limit
setting".
Figure 29
WARNING: Do not use hand held
transmitters to program primary
and secondary limits. Only the
cycle button should be used until
final set up is complete to avoid
damage to actuators and voiding
warranty.