Appendix B. Environmental Specifications

Unless otherwise noted on individual specification pages, the following
environmental specifications, based on an altitude from sea level to 2134 meters
(7000 feet), apply:
Figure B-1. Table - Environmental Specifications
Note:
© Copyright IBM Corp. 2002, 2004
Environment, Operating:
Temperature
Relative Humidity
Maximum Dew Point
Environment, Nonoperating:
Temperature
Rel Humidity
Maximum Wet Bulb
Maximum Dew Point
Environment, Shipping:
Temperature
Relative Humidity
Maximum Wet Bulb
Environment, Storage: All Models
Temperature
Relative Humidity
Maximum Wet Bulb
Prior to the installation of an IBM system, careful consideration should be
given to the computer room environment. If there is any question about
potential corrosive gases or level of particulates, contact your IBM
representative for assistance in monitoring the environment.
10° to 35°C (50°F to 95°F)
20% - 80%
21°C (70°F)
10°C to 52°C (50°F to 125°F)
8% - 80%
27°C (80°F)
21°C (70°F)
-40°C to 60°C (-40°F to 140°F)
5% - 100% (no condensation)
29°C (84°F)
1°C to 60°C (34°F to 140°F)
5% -80%
29°C (84°F)
B-1