v Raised floor cutouts should be protected by electrically nonconductive molding,
v Use Figure 2-5 on page 2-7 to install the panels in the proper positions.
Casters
The following illustration shows the physical dimensions around the casters. When
planning for both the movement and positioning of the system, be aware that each
caster swivels in a circle slightly larger than 125 mm (5 in) in diameter. Exercise
caution when working around floor cutouts.
131.6 mm
Figure 2-6. Frame-Caster Dimensions
2-8
zSeries 800: Installation Manual for Physical Planning
appropriately sized, with edges treated to prevent cable damage and to prevent
casters from rolling into the floor cutouts.
When cutting the panels, you must adjust the size of the cut for the thickness of
the edge molding you are using. The dimensions shown are finished dimensions.
Frame - Caster Dimensions
64.2 mm
(2.5 in)
(5.2 in)
Swivel Diameter
64.2 mm
(2.5 in)
136 mm
(5.35 in)
Level 04a, June 21, 2004
33.2 mm
(1.3 in)