8-5-4. Wiring connection
1. Remove the valve cover from the outdoor unit.
2. Connect the connecting cable to the terminal as
identified with their respective matched numbers on
the terminal block of indoor and outdoor unit.
3. When connecting the connecting cable to the
outdoor unit terminal, make a loop as shown in the
installation diagram of indoor and outdoor unit, to
prevent water coming in the outdoor unit.
4. Insulate the unused cords (conductors) from any
water coming in the outdoor unit. Proceed them so
that they do not touch any electrical or metal parts.
<Stripping length of connecting cable>
For RAS-07GAH-E
Terminal block
70 mm
Earth line
10 mm
Terminal
screw
10 mm
Connecting
60 mm
cable
Fig. 8-5-9
For RAS-07GA-E, RAS-07GAX
Terminal block
60 mm
10 mm
Earth line
10 mm
Connecting
cable
50 mm
Fig. 8-5-10
CAUTION
Screw
Earth
line
Cord clamp
1(L) 2(N)
Terminal
screw
Screw
Earth
line
Cord clamp
For RAS-10GAH-E
70 mm
10 mm
Earth line
10 mm
60 mm
For RAS-10GA-E, RAS-10GAX, RAS-10GAX-V
100 mm
10 mm
Earth line
10 mm
40 mm
CAUTION
• Wrong wiring connection may cause some
electrical parts burn out.
• Be sure to comply with local codes on running
the wire from indoor unit to outdoor unit (size of
wire and wiring method etc.)
• Every wire must be connected firmly.
NOTE
• Wire type: H07 RN-F or 245 IEC66 (2.0 mm
more)
− 47 −
FILE NO. SVM-06037
Terminal block
Terminal
screw
Screw
Connecting
cable
Cord clamp
Fig. 8-5-11
Terminal block
1(L) 2(N)
Terminal
screw
Screw
Connecting
cable
Cord clamp
Fig. 8-5-12
Earth
line
Earth
line
2
or