Install Electrical Connections; High- -Voltage Connections; Routing Power Leads Into Unit; Connecting Ground Lead To Unit Ground - Payne PA3Z Installation Instructions Manual

13 seer single-packaged air conditioner system with r-22 refrigerant single and three phase 2 to 5 nominal tons (sizes 024 -060)
Hide thumbs Also See for PA3Z:
Table of Contents

Advertisement

Table 2 – Minimum Airflow for Safe
Electric Heater Operation
Minimum Airflow (CFM)
Unit Size
5kW
7.5kW
024
400
550
030
450
600
036
450
600
042
450
600
049
450
600
048
450
600
060
450
600
Step 7 — Install Electrical Connections
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
The unit cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of personal
injury if an electrical fault should occur. This ground may
consist of an electrical wire connected to the unit ground
screw in the control compartment, or conduit approved for
electrical ground when installed in accordance with NEC,
ANSI/NFPA ANSI/NFPA 70 American National Standards
Institute/National Fire Protection Association (latest edition)
(in Canada, Canadian Electrical Code CSA C22.1) and local
electrical codes.
CAUTION
!
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the
unit being installed.
1. Make all electrical connections in accordance with NEC
ANSI/NFPA ANSI/NFPA 70 (latest edition) and local
electrical codes governing such wiring. In Canada, all
electrical connections must be in accordance with CSA
standard C22.1 Canadian Electrical Code Part 1 and
applicable local codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between
field- -supplied electrical disconnect switch and unit. DO
NOT USE ALUMINUM WIRE.
3. Be sure that high- -voltage power to unit is within
operating voltage range indicated on unit rating plate. On
3- -phase units, ensure phases are balanced within 2
percent. Consult local power company for correction of
improper voltage and/or phase imbalance.
4. Do not damage internal components when drilling
through any panel to mount electrical hardware, conduit,
etc.

HIGH- -VOLTAGE CONNECTIONS

The unit must have a separate electrical service with a
field- -supplied, waterproof disconnect switch mounted at, or within
sight from the unit. Refer to the unit rating plate, NEC and local
codes for maximum fuse/circuit breaker size and minimum circuit
amps (ampacity) for wire sizing.
The field- -supplied disconnect may be mounted on the unit over
the high- -voltage inlet hole when the standard power and
low- -voltage entry points are used. See Fig. 6 and 7 for acceptable
location.
10kW
15kW
20kW
650
X
X
800
850
X
800
850
900
800
850
900
800
850
900
800
850
900
800
850
900
Operation of unit on improper line voltage constitutes abuse and
may cause unit damage that could affect warranty.

ROUTING POWER LEADS INTO UNIT

Use only copper wire between disconnect and unit. The
high- -voltage leads should be in a conduit until they enter the unit;
conduit termination at the unit must be watertight. Run the
high- -voltage leads through the hole on the control box side of the
unit (See Fig. 7). When the leads are inside the unit, run leads to
the control box (See Fig. 8). For single- -phase units, connect leads
to the black and yellow wires (See Fig. 9).

CONNECTING GROUND LEAD TO UNIT GROUND

Connect the ground lead to the chassis using the unit ground in the
control box (See Fig. 8 and 9).
ROUTING CONTROL POWER WIRES (24- -V)
Form a drip- -loop with the thermostat leads before routing them
into the unit. Route the thermostat leads through grommeted hole
provided in unit into unit control box (See Fig. 7). Connect
thermostat leads and unit power leads as shown in Fig. 9, 10 and
11.
Route thermostat wires through grommet providing a drip- -loop at
the panel. Connect low- -voltage leads to the thermostat as shown in
Fig. 10 & 11.
The unit transformer supplies 24- -v power for complete system
including accessory electrical heater. Transformer is factory wired
for 230- -v operation.

ACCESSORY ELECTRIC HEAT WIRING

Refer to accessory electric heat installation instructions for
information on installing accessory electric heat. Accessory electric
heat wiring is shown in Fig. 17 and 18.
HIGH-VOLTAGE POWER
WIRING ENTRY HOLE
Fig. 7 - - Unit Electrical Connection
6
LOW-VOLTAGE WIRING
ENTRY HOLE
A05198

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pa3z024Pa3z030Pa3z036Pa3z042Pa3z049Pa3z048 ... Show all

Table of Contents