High Altitude Information - Lennox G61MPV?36B?045 Installation Instructions Manual

G61mpv series units
Hide thumbs Also See for G61MPV?36B?045:
Table of Contents

Advertisement

Manifold Pressure Measurement & Adjustment
Supply Pressure Measurement
A threaded plug on the inlet side of the gas valve provides
access to the supply pressure tap. Remove the threaded
plug, install a field−provided barbed fitting and connect a
manometer to measure supply pressure. Replace the
threaded plug after measurements have been taken.
Manifold Pressure Measurement
To correctly measure manifold pressure, the differential
pressure between the positive gas manifold and the nega-
tive burner box must be considered. Use pressure test
adapter kit (available as Lennox part 10L34) to assist in
measurement.
1 − Remove the threaded plug from the outlet side of the
gas valve and install a field−provided barbed fitting.
Connect test gauge +" connection to barbed fitting to
measure manifold pressure.
Model Number
045, 070, 071, 090,
110, 135
091, 111

High Altitude Information

NOTE − In Canada, certification for installations at eleva-
tions over 4500 feet (1372 m) is the jurisdiction of local au-
thorities.
The manifold pressure may require adjustment to ensure
proper operation at higher altitudes. Refer to table 32 for
manifold pressure and table 33 for required pressure
High Altitude
Orifice Kit
Natural Gas
Input
Only
7501−10,000 ft.
2000−4500 ft.
−045
44W51
−070
44W51
−071
44W51
−090
44W51
−091
47M82
−110
44W51
−111
47M82
−135
44W51
1
High Altitude Orifice Kit is required and must be ordered separately for applications from 7501 to 10,000 ft.
Manifold Pressure (Outlet)
0−2000
Fuel
Low
High
Fire
Fire
Natural
1.7
3.5
Propane 4.9
10.0
Natural
1.7
3.5
Propane 4.9
10.0
Conversion Kit Requirements
High Altitude Pressure Switch Kit
ORDER TWO EACH
4501−7500 ft.
− − −
− − −
− − −
− − −
75M22
75M22
− − −
75M22
26W85
26W85
− − −
56M23
56M22
56M22
− − −
56M93
2 − Tee into the gas valve regulator vent hose and connect
test gauge −" connection.
3 − Start unit on low heat (68% rate) and allow 5 minutes
for unit to reach steady state.
4 − While waiting for the unit to stabilize, notice the flame.
Flame should be stable and should not lift from burner.
Natural gas should burn blue.
5 − After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in table
32.
6 − Repeat steps 3, 4 and 5 on high heat.
NOTE − Shut unit off and remove manometer as soon as an
accurate reading has been obtained. Take care to remove
barbed fitting and replace threaded plug.
Do not attempt to make adjustments to the gas valve.
TABLE 32
Altitude (feet)
2001−4500
4501−5500
Low
High
Low
High
Fire
Fiire
Fire
Fiire
1.7
3.5
1.7
3.5
4.9
10.0
4.9
10.0
1.7
3.4
1.7
3.3
4.9
10.0
4.9
10.0
switch changes and conversion kits at varying altitudes.
The combustion air pressure switches are factory−set and
require no adjustment.
NOTE − A natural to L.P. propane gas changeover kit is nec-
essary to convert this unit. Refer to the changeover kit
installation instruction for the conversion procedure.
TABLE 33
LPG/Propane Kit
7501−10,000 ft.
0−7500 ft.
− − −
44W48
56M23
44W48
56M21
44W48
56M21
44W48
26W86
44W48
75M22
44W48
56M23
44W48
56M93
44W48
Page 57
CAUTION
5501−6500
6501−7500
Low
High
Low
High
Fire
Fiire
Fire
Fiire
1.7
3.5
1.7
3.5
4.9
10.0
4.9
10.0
1.7
3.2
1.7
3.1
4.9
10.0
4.9
10.0
LPG/Propane to
Natural Gas Kit
7501−10,000 ft.
0−7500 ft.
44W50
44W49
44W50
44W49
44W50
44W49
44W50
44W49
44W50
44W49
44W50
44W49
44W50
44W49
44W50
44W49
7501−10000
Low
High
Fire
Fiire
1.7
3.5
4.9
10.0
1.7
3.5
4.9
10.0
1
7501−10,000 ft.
44W49 + 44W51
44W49 + 44W51
44W49 + 44W51
44W49 + 44W51
44W49 + 47M82
44W49 + 44W51
44W49 + 47M82
44W49 + 44W51