IBM 11000VA Manual page 6

Lcd 5u rack uninterruptible power supply
Table of Contents

Advertisement

Table 2. Specifications (continued)
Communications and management
USB port
RS-232 serial port
Ethernet port
Environmental Monitoring Probe
Surge protection and filtering
Surge energy rating
Filtering
Battery run times and recharge times
Table 3 lists the expected period during which the 11000VA UPS will operate solely on batteries.
Table 3. IBM 11000VA UPS runtime chart
Load
Percent load
VA
50%
5500
100%
11000
Note: Battery backup times are approximate and can vary with equipment, configuration, battery age, and
temperature.
Physical specifications and operating environment
The physical specifications of the 5U uninterruptible power supply are as follows:
Height: 212 mm (8.3 in.)
Width: 483 mm (19 in.)
Depth: 740 mm (29.1 in.)
Weight: 99 kg (218 lb)
The physical specifications of the 3U Extended Battery Module are as follows:
Height: 127 mm (5.0 in)
Width: 483 mm (19 in.)
Depth: 740 mm (29.1 in.)
Weight: 79 kg (174 lb)
The IBM 11000VA LCD 5U Rack UPS is supported in the following operating environment:
Temperature: 0 - 40.0° C (32 - 104° F) at 0 - 2,000 m (0 - 6,600 ft)
Relative humidity: 5 - 95%
Maximum altitude: 3,048 m (10,000 ft)
IBM 11000VA LCD 5U Rack Uninterruptible Power Supply
Watts
Run time with standard internal
battery only
5000
14 minutes
10000
5 minutes
Yes
Yes
Optional using Network Management Card, 46M4110
Optional Environmental Monitoring Probe, 46M4113
1300 Joules
ANSI/IEEE C62.41; 1991 CATEGORYB3 (SURGE)
Run time on batteries
Run time with internal battery plus
External Battery Module (EBM)
35 minutes
14 minutes
6

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents