Inlet Piping - Amana 10759833 Installation Instructions Manual

Two-stage variable speed
Table of Contents

Advertisement

9.
The unit must be connected to the building piping by
one of the following methods:
Rigid metallic pipe and fittings
Semirigid metallic tubing and metallic fittings (Alumi-
num alloy tubing must not be used in exterior loca-
tions)
Listed gas appliance connectors used in accor-
dance with the terms of their listing that are com-
pletely in the same room as the equipment
Protect connectors and semirigid tubing against
physical and thermal damage when installed. En-
sure aluminum-alloy tubing and connectors are
coated to protect against external corrosion when in
contact with masonry, plaster, or insulation, or sub-
jected to repeated wetting by liquids such as water
(except rain water), detergents, or sewage.

Inlet Piping

When the gas piping enters through the right side of the
furnace, the installer must supply the following fittings
(starting from the gas valve):
• 90 degree elbows (2).
• Close nipple.
• Straight pipe to reach the exterior of the furnace.
A ground joint union, drip leg, and manual shutoff valve
must also be supplied by the installer. In some cases, the
installer may also need to supply a transition piece from
1/2" to another pipe size.
When the gas piping enters through the left side of the
furnace, the installer must supply the following fittings
(starting from the gas valve):
Straight pipe to reach the exterior of the furnace.
A ground joint union, drip leg, and manual shutoff valve
must also be supplied by the installer. In some cases,
the installer may also need to supply a transition piece
from 1/2 inch to another pipe size.
Gas Inlet Through Furnace Right Side
Gas Supply and Piping
21
21
Gas Inlet Through Furnace Left Side
Gas Inlet Through Furnace Bottom Side
Gas Inlet Through Furnace Top Side

Advertisement

Table of Contents
loading

Table of Contents