Propane Gas Tanks and Piping
Sizing Between First and Second Stage Regulator*
Maximum Propane Capacities listed are based on 2 psig pressure drop at 10 psig setting.
Capacities in 1,000 BTU/hour.
Pipe or
Tubing
Length,
3/8"
Feet
10
730
20
500
30
400
40
370
50
330
60
300
80
260
100
220
125
200
150
190
175
170
200
160
To convert to capacities at 15 psig settings - multiply by 1.130
To convert to capacities at 5 psig settings - multiply by 0.879
Sizing Between Single or Second Stage Regulator and Appliance*
Maximum Propane Capacities Listed are Based on 1/2" W.C. pressure drop at 11" W.C. setting.
Capacities in 1,000 BTU/hour.
Pipe or
Tubing
Tubing Size, O.D. Type L
Length,
3/8"
1/2"
Feet
10
39
92
20
26
62
30
21
50
40
19
41
50
18
37
60
16
35
80
13
29
100
11
26
125
10
24
150
9
21
200
8
19
250
8
17
*Data in accordance with NFPA pamphlet NO. 54
Tubing Size, O.D. Type L
1/2"
5/8"
1,700
3,200
1,100
2,200
920
2,000
850
1,700
770
1,500
700
1,300
610
1,200
540
1,000
490
900
430
830
400
780
380
730
5/8"
3/4"
7/8"
199
329
501
131
216
346
107
181
277
90
145
233
79
131
198
72
121
187
62
104
155
55
90
138
48
81
122
43
72
109
39
66
100
36
60
93
24
24
Nominal Pipe Size
3/4"
7/8"
5,300
8,300
3,700
5,800
2,900
4,700
2,700
4,100
2,400
3,700
2,200
3,300
1,900
2,900
1,700
2,600
1,400
2,300
1,300
2,100
1,200
1,900
1,100
1,800
Nominal Pipe Size
Schedule 40
1-1/8"
1/2"
3/4"
935
275
567
630
189
393
500
152
315
427
129
267
376
114
237
340
103
217
289
89
185
255
78
162
224
69
146
202
63
132
187
54
112
172
48
100
Schedule 40
1/2"
3/4"
3,200
7,500
2,200
4,200
1,800
4,000
1,600
3,700
1,500
3,400
1,300
3,100
1,200
2,600
1,000
2,300
900
2,100
830
1,900
770
1,700
720
1,500
1"
1-1/4" 1-1/2"
1,071
2,205
3,307
732
1,496
2,299
590
1,212
1,858
504
1,039
1,559
448
913
1,417
409
834
1,275
346
724
1,066
307
630
976
275
567
866
252
511
787
209
439
665
185
390
590