2 INSTALLATION DIAGRAM OF INDOOR AND OUTDOOR UNITS

The indoor unit shall be
installed so that the top of the
indoor unit is positioned at
least 2 m high. Also, avoid
putting anything on the top of
the indoor unit.
2 m or more
CAUTION
Install in rooms that
3
are 5 m
or larger. If a
leak of refrigerant gas
occurs inside the
room, an oxygen
deficiency can occur.
b Wireless remote controller
f Remote controller
holder mounting
screw
Before installing the wireless
remote controller
• With the remote controller
cover removed, correctly
load the supplied batteries
while observing their
polarity.
b Wireless remote controller
Cover
c Batteries
When installing the outdoor unit,
leave open in at least two of
directions (A), (B), (C) and (D)
shown in the right figure.
• If the system will be used in cooling mode when the outdoor temperature is below zero, take measures to ensure that the
drain water does not freeze.
• When the outdoor unit is installed in a place that is always exposed to strong winds like on the coast or on a high story of
a building, secure the normal fan operation using a duct or a wind shield.
CAUTION
(RAS-***-ND model only)
• Use care to avoid burns. A heater is installed on the base plate of the outdoor unit. When the outside air temperature is low,
the heater runs to warm the base plate even if the unit is not operating so that snow does not accumulate inside the outdoor
unit.
• Do not use the supplied drain nipple for draining water. Drain the water from all the drain holes directly. Provide a space of at
least 50 cm under the outdoor unit so that the draining water does not freeze and block the drain holes.
EN
160 mm or
more
e Mounting screw
d Remote controller holder
80 mm or more only
when unobstructed to
the front and both sides
In principle,
leave open
(C)
100 mm or
more from
wall
200 mm or
more
(B)
Ensure sufficient space
to allow drainage
Hook
70 mm or more
Hook
Hook
Hook
Air filters
Y
50 mm or more
from wall
(D)
power cord
Extension drain hose
4
For the rear left and left
piping
a Installation
plate
180 mm or
more
Insert the cushion between
the indoor unit and wall, and
tilt the indoor unit for better
installation work.
Do not allow the drain hose
to become slack.
Connecting
cable
Z
Shield pipe
(for extension
drain hose)
Make sure the drain hose is
sloped downward.
The auxiliary piping can be
connected at the left, rear
left, rear right, right, bottom
right or bottom left as shown
below.
Right
As shown in the
figure, position
Rear
power cord and
right
connecting
Bottom right
cable
downward, and
lead out along
piping
connection port.
Insulate the refrigerant pipes
separately, not together.
(A)
250 mm or
more from wall
8 mm thick heat resisting
Connecting cable
polyethylene foam
Wall
Cut the piping hole
slightly sloped
Rear left
Left
Bottom left