Packed valve handling precautions
• Open the valve stem until it touches the stopper. Once it is in contact with the stopper, refrain from applying any more force than is
necessary.
• Securely tighten the valve stem cap with torque in the following table:
Gas side
(Dia. 12.7 mm)
Gas side
(Dia. 9.52 mm)
Liquid side
(Dia. 6.35 mm)
Service port
Wiring Connection
1.
Remove the valve cover, the electric parts cover and the cord clamp from the outdoor unit.
2.
Connect the connecting cable to the terminal as identified by the matching numbers on the terminal block of indoor and outdoor
unit.
3.
Insert the power cord and the connecting cable fully into the terminal block and secure it tightly with screws.
4.
Use vinyl tape, etc. to insulate the cords which are not going to be used. Locate them so that they do not touch any electrical or
metal parts.
5.
Secure the power cord and the connecting cable with the cord clamp.
6.
Attach the electric parts cover and the valve cover on the outdoor unit.
Stripping length of connecting cable
Terminal block
1
2
3
Connecting
cable
Model
Power source
Maximum running current
Installation fuse rating
Power cord
Connecting cable
CAUTION
• Incorrect wiring connection may cause electrical parts to burn out.
• Be sure to comply with local regulations/codes when running the wire from outdoor unit to indoor unit. (Size of wire and wiring
method etc.)
• Every wire must be securely connected.
• If incorrect or incomplete wiring is carried out, fire or smoke may result.
• Prepare the power supply for the exclusive use of the air conditioner.
33 to 42 N·m
(3.3 to 4.2 kgf·m)
33 to 42 N·m
(3.3 to 4.2 kgf·m)
14 to 18 N·m
(1.4 to 1.8 kgf·m)
14 to 18 N·m
(1.4 to 1.8 kgf·m)
L
N
Power cord
RAS-07PKVP-E
RAS-10PKVP-E
RAS-07PKVP-ND
RAS-10PKVP-ND
1 2 3
10
10
50
40
Earth line
Connecting
cable
RAS-13PKVP-E
RAS-13PKVP-ND
220–240 V ~50 Hz
220–230 V ~60 Hz
9.5 A
16 A breaker or fuse (all types can be used)
H07RN-F or 60245IEC66 (1.5 mm
Wire type: H07RN-F or 60245IEC66 (1.0 mm
17
Hexagon wrench
is required.
4 mm
10
L N
10
50
40
Earth line
Power cord
RAS-16PKVP-E
RAS-18PKVP-E
RAS-16PKVP-ND
RAS-18PKVP-ND
2
)
2
)
EN