E5GN
Characteristics Table
-- continued from previous page
Weight
Protective structure
Memory protection
EMC
Approval standards


COMMUNICATIONS SPECIFICATIONS

Transmission path connection
Communications method
Synchronization method
Baud rate
Transmission code
Data bit length
Stop bit length
Error detection
Flow control
Interface
Retry function
Communications buffer
Note: The baud rate, data bit length, stop bit length, or vertical parity can be individually set using the communications setting level.
Approx. 90 g
Front Panel
NEMA4 for indoor use (equivalent to IP66)
Rear Case
IP20
Terminals
IP00
EEPROM (non-volatile memory) (number of writes: 100,000)
Emission Enclosure:
Emission AC Mains:
Immunity ESD:
Immunity RF-interference:
Immunity Conducted Disturbance:
Immunity Burst:
UL3121-1, CSA22.2 No. 14, E.B.1402C
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1)
Conforms to VDE0106/part 100 (Finger Protection), when the terminal cover is mounted.
Multiple points
RS-485 (two-wire, half duplex)
Start-stop synchronization
1,200/2,400/4,800/9,600/19,200 bps
ASCII
7 or 8 bits
1 or 2 bits
Vertical parity (none, even, odd)
Frame check sequence (FCS): with SYSMAC WAY
Block check character (BCC): with CompoWay/F
Not available
RS-485
Not available
40 bytes
Mounting bracket: approx. 10g
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
ENV50140:
10 V/m (amplitude modulated,
80 MHz to 1 GHz) (level 3)
10 V/m (pulse modulated, 900 MHz)
ENV50141:
10 V (0.15 to 80 MHz) (level 3)
EN61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
E5GN

Hide quick links:

Advertisement

Table of Contents
loading