Omron E5GN Instructions Manual page 19

Compact and intelligent 1/32 din temperature controller with communications function
Hide thumbs Also See for E5GN:
Table of Contents

Advertisement

E5GN
Communications Setting Level
Set the E5CN/E5GN communications specifications in the communications setting level. For setting communications parameters, use the
E5CN/E5GN panel. The communications parameters and their settings are listed in the following table.
Parameter
Communications unit No.
Baud rate
Data bits
Stop bits
Parity
Note: The highlighted values indicate default settings.
Before executing communications with the E5CN/E5GN, set the
communications unit No., baud rate, etc., through key operations
as described below. As for other operations, refer to the relevant
Operation Manual.
1. Press the
key for at least three seconds in the "operation
level." The level moves to the "initial setting level."
2. Press the
key for less than one second. The "initial
setting level" moves to the "communications setting level."
3. Pressing the
key advances the parameters as shown
in the following figure.
4. Press the
or
keys to change the parameter setups.
Communications
unit No.
Baud rate
Data bits
Stop bits
Parity
Note: On the E5GN, the
Key is the
Set each communications parameter to match those of the
communicating personal computer.
Displayed characters




 
Key.
Set (monitor) value
0 to 99
1.2/2.4/4.8/9.6/19.2 (kbps)
7/8 (bit)
1/2
None, even, odd
Communications Unit No. (  )
When communicating with the host computer, the unit number
must be set in each Temperature Controller so that the host
computer can identify each Temperature Controller. The number
can be set in a range from 0 to 99 in increments of 1. The default
setting is 1. When using more than one Unit, be careful not to
use the same number twice. Duplicate settings will cause
malfunction. This value becomes valid when the power is turned
OFF and ON again.
Baud Rate (  )
Use this parameter to set the speed of communications with the
host computer. It can be set to one of the following values; 1.2
(1200 bps), 2.4 (2400 bps), 4.8 (4800 bps), 9.6 (9600 bps), and
19.2 (19200 bps).
This setting becomes valid when the power is turned OFF and
ON again.
Data Bits (   )
Use this parameter to change the communications data bit length
to 7 bits or 8 bits.
Stop Bits (  )
Use this parameter to change the communications stop bit to 1 or
2.
Parity (  )
Use this parameter to set the communications parity to None,
Even, or Odd.
E5GN
Set value
0.1 to 99
1.2/2.4/4.8/9.6/19.2
7/8 (bit)
1/2 (bit)
 /   / 

Hide quick links: