Fault Findings - Stanley BRANDON 60K User Manual

Brandon 60k/80k/100k oil fired cooker
Table of Contents

Advertisement

PROBLEM
1.
Poor Flue Draught:
2.
Excessive Flue Draught
3.
Down Draught:
4.
Cooker Smoking:
5.
Hot Plate Not Heating:
6.
Oven Not Heating:
7.
Radiators Not Heating:
8.
Domestic Hot Water
Cylinder not getting
hot enough:
9.
Intermittent Performance: (a) Cooker starved of primary air.
10. Domestic Hot Water
Rusty:
It is of the utmost importance to keep the flue pipe and chimney clear of deposits. Blocked or
partially obstructed flueways and chimneys will cause dangerous fumes to be emitted into the room,
these may well be invisible.
Manufactured by
Waterford Stanley Ltd.,
Unit 210, IDA Industrial Estate, Cork Road,
Waterford, Ireland.
Tel: (051) 302300 Fax (051) 302315
www.waterfordstanley.com

FAULT FINDINGS

CAUSE
(a) Obstruction.
(b) Chimney too low.
(c) Chimney too wide.
(d) Crack in wall.
(e) No flue liner
(a) High chimney.
(a) High trees
(b) High buildings
(c) Low chimney.
(d) Positive pressure zone.
(a) Insufficient primary air.
(b) Chimney choked.
(c) Downdraught.
(d) Poor combustion.
(a) Burner cutting out.
(b) Utensils not flat.
(a) Flueways blocked with soot.
(a) Circulating pump not working.
(b) Room thermostat set too low
(c) Air in system.
(d) Pipe system faulty.
(e) Excessive number of radiators
(f) Radiator valves not balanced.
(g) By-pass incorrectly set.
(a) Cylinder too large.
(b) Flow pipe too large.
(c) 'Balancing valve' is closed.
(d) Cylinder thermostat set too low.
(e) Circulating pump not working.
(f) Motorised valve not opening
(b) Extraction fan in room.
(c) Dirt in nozzle.
(d) Dirty burner.
(e) Faulty Thermistor/Thermocouple (e) Replace if defective.
(f) Dirty flueways.
(g) Dirty Oil Filter
(h) Worn nozzle
(a) Leak in indirect cylinder.
(b) Incorrect cylinder fitted.
REMEDY
(a) Clear and clean.
(b) Raise height above ridge.
(c) Fit flue liner 150mm (6")
(d) Repair cracks.
(e) Fit flue liner
(a) Fit draught stabiliser venting to the outside atmosphere.
(a) Raise chimney height.
(b) Raise chimney height.
(c) Raise chimney height.
(d) Check flue termination
(a) Provide additional room air inlet or adjust burner air intake.
(b) Clean chimney.
(c) Raise chimney height.
(d) Check air supply.
(a) Increase cooker thermostat setting.
(b) Use machined based utensils.
(a) Clean out.
(a) Check and replace if defective.
(b) Increase setting
(c) Bleed system.
(d) Check pipe sizes and circuit.
(e) Turn off un-needed radiators.
(f) Adjust valves to give an even flow.
(g) Adjust by-pass valve
(a) Use 180 litre cylinder.
(b) Use 28mm bore pipe.
(c) Open 'balancing valve'.
(d) Increase thermostat setting.
(e) Check and replace if defective.
(f) Check and replace if defective.
(a) Provide air inlet in room.
(b) Provide additional air inlet in room.
(c) Clean or replace nozzle.
(d) Service burner.
(f) Clean flueways.
(g) Clean or replace
(h) Replace nozzle
(a) Replace cylinder.
(b) Check with installer.
14
N00333AXX DP 100421 Rev 007

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Brandon 80kBrandon 100k

Table of Contents