Samsung DH094EAMC Service Manual page 83

System air conditioner
Hide thumbs Also See for DH094EAMC:
Table of Contents

Advertisement

Troubleshooting
12-2-8 Cond. temperature sensor error
1. Checklist :
1) Is the sensor connector connected correctly?
2) Is the sensor placed correctly?
3) Does the both terminal of sensor satisfy the resistance value in accordance with temperature?
4) Is the resistance value of sensor connection pull_up correct?
2. Troubleshooting procedure
Is the sensor connector connected
correctly in accordance with a color?
Is the temperature sensor connected
correctly without separation?
Does the both terminal of sensor
satisfy the resistance
value in accordance with temperature?
(Refer to the R/T TABLE)
Is the resistance value
of sensor connection pull_up 18.2K?
400.0
350.0
300.0
250.0
200.0
150.0
100.0
12-10
Yes
Yes
Yes
Yes
50.0
0.0
Reconnect the sensor connector.
No
Change the position of sensor.
No
No
Exchange the sensor.
No
No
Exchange the PCB.
Exchange the PCB.
Normal operation
Exit
Samsung Electronics

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dh052easUh052easAqv24awaxDh070easUh070eas

Table of Contents