Clearance To Combustibles; Floor Protection - Regency F250B Owners & Installation Manual

Hume freestanding wood fire
Hide thumbs Also See for F250B:
Table of Contents

Advertisement

Flo-Met
Super Single
*(1)
A
400mm
B
210mm
C
200mm
D
181mm
E
123mm
F
400mm
G
1015mm
H
1120mm

Floor Protection

A combustible fl oor must be protected by non-combustible material (like
tile, concrete board, or as defi ned by local codes) extending beneath
the heater as follows;
From Sides:
123mm
From Front:
400mm
From Back:
181mm
The fl oor protector should consist of 6mm thick cement fi bre sheet
which has a thermal resistance of 0.8m
fi bre sheet.
IMPORTANT
* (1) The Flomet Super Single fl ue kit must be installed with a 130
900mm stainless refl ective shield between decromesh.
* (2) The AHD Special Insulated fl ue kit must be installed with a
40mm air gap around the fl ue to any combustible surfaces and the
ceiling ring must be spaced as such to provide an air gap of 20mm to
the ceiling. The AHD Special Insulated fl ue kit must be installed with
a perforated ceiling plate and 250mm dia. x 195mm high heatshield
positioned directly above the ceiling plate.
The fl ue pipe shall extend not less than 4.6m above the top of the fl oor protector.
NOTE: Installation must be carried out by a licensed installer in accordance
with AS/NZS 2918:2001.
NOTE: A minimum clearance of 180mm (fl at wall) or 200mm (corner wall) must be retained for all wall surfaces to allow for fan access and maintenance.
Regency Hume Freestanding Wood Fire
MINIMUM CLEARANCE TO
COMBUSTIBLE MATERIALS
Hawkwind
AHD Special
Standard
Insulated
*(2)
400mm
450mm
180mm
300mm
200mm
200mm
181mm
181mm
123mm
123mm
400mm
400mm
1015mm
1015mm
1120mm
1120mm
2
k/w for 4mm sheets of cement
o
x
INSTALLATION
7