( 3 ) Combined operation mode 1 (Pr. 79 "operation mode selection" = 3)
The start signal is an external signal.
The frequency setting signal is set using the optional control
panel or parameter unit.
Preparation
y Start signal............... Switch, relay, etc.
y Operation unit .......... Control panel (FR-PA02
y Connection cable..... Refer to (1) PU operation mode.
y FR-E5P (option)....... Refer to (1) PU operation mode.
( 4 ) Combined operation mode 2 (Pr. 79 "operation mode selection" = 4)
The start signal is entered from the operation command key
of the optional control panel.
The frequency setting signal is set using the external
frequency setting signal.
Preparation
y Frequency.................. 0 to 5V, 0 to 10V, 4 to 20mA DC
setting signal
y Operation unit ............ Control panel (FR-PA02
y Connection cable....... Refer to (1) PU operation mode.
y FR-E5P (option)......... Refer to (1) PU operation mode.
( 5 ) Communication operation mode
(Pr. 79 "operation mode selection" = 0 or 1)
Communication operation can be performed by connecting a personal computer and
the PU connector with the RS-485 communication cable.
Preparation
y Connection cable ..........................Connector: RJ45 connector
y Personal computer
y RS-485, RS-232C converter.........T o be prepared w hen the com m unication port of the
parameter unit (FR-PU04)
signals from an external
potentiometer or from outside the
inverter
parameter unit (FR-PU04)
Cable: Cable conforming to EIA568
(e.g. 10BASE-T cable)
personal com puter has R S -232C specifications.
50
) or
-02
) or