Mitsubishi Electric FR-E500 Instruction Manual page 169

Fr-e500 series transistorized inverter
Hide thumbs Also See for FR-E500:
Table of Contents

Advertisement

<Operation procedure>
y When using the control panel (FR-PA02-
1) Select the PU operation mode.
2) Set the running frequency.
3) Press the
SET
4) Read Pr. 900 "FM terminal calibration".
5) Press the
FWD
6) Hold down the
(Depending on the setting, it may take some time unit the pointer moves.)
7) Press the
SET
STOP
8) Press the
RESET
Note: 1. Pr. 900 is factory-set to 1mA full-scale or 1440 pulses/sec. FM output
frequency at 60Hz. The maximum pulse train output of terminal FM is 2400
pulses/sec.
2. When a frequency meter is connected across terminals FM-SD to monitor
the running frequency, the FM terminal output is filled to capacity at the
factory setting if the maximum output frequency reaches or exceeds 100Hz.
In this case, the Pr. 55 setting must be changed to the maximum frequency.
key.
key to run the inverter. (Motor need not be connected.)
/
key to adjust the meter pointer to a required position.
key for about 1.5 sec.
key to stop the inverter.
)