Troubleshooting - Toshiba RAV-SM1103AT-E1 Service Manual

Split type
Table of Contents

Advertisement

8-2. Troubleshooting

8-2-1. Outline of judgment
The primary judgment to check whether a trouble occurred in the indoor unit or outdoor unit is carried out with
the following method.
Method to judge the erroneous position by flashing indication on the display part of the indoor unit
(sensors of the receiving part)
The indoor unit monitors the operating status of the air conditioner, and the blocked contents of self-diagnosis
are displayed restricted to the following cases if a protective circuit works.
Lamp indication
Operation Timer
Ready
No indication at all
Operation Timer
Ready
Flash
Operation Timer
Ready
Flash
Operation Timer
Ready
Alternate flash
Operation Timer
Ready
Alternate flash
1:
These are representative examples and the check code differs according to the outdoor unit to be combined.
Check code
Power supply OFF or miswiring between receiving unit and indoor unit
E01
Receiving error
E02
Sending error
E03
Communication stop
E08
Duplicated indoor unit No.
E09
Duplicated header units of remote controller
E10
Communication error between CPUs on indoor unit P.C. board
Wire connection error between indoor units, Indoor power OFF
E18
(Communication stop between indoor master and follower or between main
and sub indoor twin)
Miswiring between indoor unit and outdoor unit or connection erorr
(Communication stop between indoor and outdoor units)
E04
Outdoor unit case thermostat work on
P01
Overflow was detected.
P10
Indoor DC fan error
P12
Outdoor unit discharge temp. error
P03
Case thermostat work on,
P04
Power error, High pressure protection
P05
Negative phase detection error
P07
Heat sink overheat error
P15
Gas leak detection error
P19
4-way valve system error (Indoor or outdoor unit judged.)
Outdoor unit high pressure protection
P20
P22
Outdoor unit: Outdoor unit fan error
P26
Outdoor unit: Inverter Idc operation
P29
Outdoor unit: Position detection error
Stopped because of error of other indoor unit in a group
P31
(Check codes of E03/L03/L07/L08)
: Go off,
Cause of tr oub le occurrence
Receiving unit
Protective device of indoor unit worked.
– 39 –
: Go on,
: Flash (0.5 sec.)
Miswiring or wire connection error
between receiving unit and indoor unit
Setup error
................
Comp. overheating
Outdoor wiring error
Protective device of
outdoor unit worked.
Outdoor unit error
Protective device of
outdoor unit worked.
*1
*1

Hide quick links: