Installation Location - Biasi Riva Plus Installation & Operation Instructions

Wall hung gas boiler for central heating supply
Table of Contents

Advertisement

6.

Installation Location

The installation location chosen must:
Comply with all clearances listed below.
Provide suitable location for the exhaust and intake venting.
Not be installed in an unheated space.
Comply with all local codes and standards.
Note: Dimensions shown are minimums. Greater clearances will simplify installation
and service.
10.0 in
2.0 in
8.0 in
15.8 in
FRONTV
WARNING: Do not install the boiler on carpeting
If the boiler is to be installed in an enclosed room with no fresh air intake, the room must have
proper vent louvers installed. There should be two louvers, place each within 12" of the ceiling
and oor respectively. Each vent will have a free area of 54 square inches.
Note: For boilers in an enclosed space
it is recommended to install a CO
detector in the boiler room.
When choosing an installation location insure the exhaust and intake pipes comply with NFPA
54. The drawing on the next page illustrates the restrictions on exhaust locations.
14 RIVA PLUS MANUAL
2.0 in
31.6 in
E I
W
15.2 in
I S
DE VIEW CLOSET
INST ALLATION
Figure 6.1
3.0 in
CLOSET INST ALLATION
MINIMUM PERM ANANT
CLEARANCE
18.0 in
CLOSET INST ALLATION
SERVICECLEARANCE
0 to 12"
Each opening free area =
1 sq. inch per 2,000 BTU/h
Outside
0 to 12"
Figure 6.2
Air Opening
Air Opening