Installation Location - Biasi Riva Combi Installation & Operation Instructions

Wall hung gas boiler for central heating and domestic hot water supply
Table of Contents

Advertisement

6. Installation Location

The installation location chosen must:
Comply with all clearances listed below.
Provide suitable location for the exhaust and intake venting.
Not be installed in an unheated space.
Comply with all local codes and standards.
Note: Dimensions shown are minimums. Greater clearances will simplify installation and
service.
10.0 in
2.0 in
8.0 in
23.8 in
FRONTV IE W
If the boiler is to be installed in an enclosed room with no fresh air intake, the room must have
proper vent louvers installed. There should be two louvers, place each within 12" of the ceiling and
floor respectively. Each vent will have a free area of 54 square inches.
Note : For boilers in an enclosed
space it is recommended to install
a CO detector in the boiler room.
14
2.0 in
35.5 in
WARNING: Do not install the boiler on carpeting
18.0 in
SIDE VIEW CLOSET
INST ALLATION
Figure 6.1
Each opening free area =
1 sq. inch per 2,000 BTU/h
Figure 6.2
3.0 in
CLOSET INST ALLATION
MINIMUM PERM ANANT
CLEARANCE
18.0
CLOSET INST ALLATION
S ERVICE CLE ARANCE
0 to 12"
Air Opening
Outside
Air Opening
0 to 12"
RIVA COMBI MANUAL - REV B