 Sensor R-T Table (Resistance-Temperature)
2. Outdoor Coil Temp. Sensor, Outdoor Air Temp. Sensor
Indoor Coil Temp. Sensor, Indoor Air Temp. Sensor
RESISTANCE : 10.0kΩ at 25°C (77°F)
RESISTANCE TOLERANCE : ±1%
TEMP.(°C)
TEMP.(°F)
-50.0
-58.0
-45.0
-49.0
-40.0
-40.0
-35.0
-31.0
-30.0
-22.0
-25.0
-13.0
-20.0
-4.0
-15.0
5.0
-10.0
14.0
-5.0
23.0
0.0
32.0
5.0
41.0
10.0
50.0
15.0
59.0
20.0
68.0
25.0
77.0
30.0
86.0
35.0
95.0
40.0
104.0
45.0
113.0
50.0
122.0
55.0
131.0
60.0
140.0
65.0
149.0
70.0
158.0
75.0
167.0
80.0
176.0
85.0
185.0
90.0
194.0
95.0
203.0
100.0
212.0
105.0
221.0
110.0
230.0
Samsung Electronics
MAX (kΩ)
CENTER (kΩ)
351.4
329.5
263.4
247.7
199.9
188.5
152.4
144.1
117.5
111.3
86.5
86.4
71.2
67.8
55.9
53.4
44.4
42.5
35.3
33.9
28.4
27.3
22.9
22.1
18.6
18.0
15.2
14.7
12.5
12.1
10.3
10.0
7.6
8.3
7.2
6.9
6.0
5.8
5.1
4.9
4.3
4.2
3.7
3.5
3.1
3.0
2.7
2.6
2.3
2.2
2.0
1.9
1.8
1.7
1.5
1.5
1.3
1.3
1.2
1.1
1.0
1.0
0.9
0.9
0.8
0.8
MIN (kΩ)
TEMP. TOLERANCE. (°F)
308.8
-1.4
232.6
-1.4
177.5
-1.4
136.0
-1.3
105.4
-1.3
82.0
-1.3
64.5
-1.3
50.9
-1.1
40.8
-1.1
32.5
-1.1
26.2
-0.9
21.2
-0.9
17.3
-0.7
14.2
-0.7
11.7
-0.7
9.7
-0.5
8.0
-0.7
6.7
-0.7
5.6
-0.9
4.7
-1.1
4.0
-1.1
3.4
-1.3
2.9
-1.4
2.5
-1.4
2.1
-1.6
1.8
-1.8
1.6
-1.8
1.7
-2.0
1.2
-2.2
1.1
-2.3
0.9
-2.3
0.8
-2.5
0.7
-2.7
Operating Instructions and Installation
1.4
1.4
1.4
1.3
1.3
1.3
1.3
1.1
1.1
1.1
0.9
0.9
0.7
0.7
0.7
0.5
0.7
0.7
0.9
1.1
1.1
1.3
1.4
1.4
1.6
1.8
1.8
2.0
2.2
2.3
2.5
2.5
2.7
11-13