Description; Application Flexibility Outdoor; Application Flexibility Indoor; Typical Indoor Unit Applications - York HB 180 Technical Manual

Commercial split-system cooling units four pipe system
Table of Contents

Advertisement

036-21323-002-C-0206

DESCRIPTION

Both the outdoor and indoor units are completely piped and
wired at the factory and are shipped ready for immediate
installation. Only the interconnecting liquid and suction lines,
control wiring, and the main power wiring are required to
complete the installation. Every outdoor unit is dehydrated,
evacuated, leak tested and pressure tested at 450 psig
before being pressurized with a holding charge of refrigerant-
22 for shipment and/or storage.
To eliminate the costly cabinet deterioration problems usually
associated with outdoor equipment, all sheet metal parts are
constructed of commercial grade (G90) galvanized steel.
After fabrication, each part is thoroughly cleaned to remove
any grease or dirt from its surfaces. The parts that will be
exposed to the weather are then coated with a desert sand
powder paint to assure a quality finish for many years. This
coating system has passed the 750-hour, salt spray test per
ASTM Standard B117.

APPLICATION FLEXIBILITY OUTDOOR

The outdoor units are lightweight and can be installed on
almost any roof.
Units can be lifted using nylon straps with hooks at the holes
provided in the base rails, or they may be lifted with a forklift
through the slotted openings in the base rails.
A quality appearance and low sound levels make these units
suitable for most ground level locations.
Suction
Model HB
Press. &
PSIG ºF
61.5 35
68.5 40
240
76
45
84
50
61.5 35
68.5 40
180
76
45
84
50
Unitary Products Group
CONDENSER ONLY CAPACITY
Temperature of Air on Condenser Coil, ºF
65
75
MBH
KW*
MBH
255
17.2
243
275
17.6
263
296
18.1
283
319
18.7
305
191
12.7
182
207
13.0
197
224
13.3
214
241
13.7
230
*Power consumption includes outdoor fans and compressors only.

APPLICATION FLEXIBILITY INDOOR

A I R O U T
( S t d . A r r a n g e m e n t )
B L O W E R
S E C T I O N
R E T U R N A I R
D U C T F L A N G E
A I R
I N
F I L T E R S
V E R T I C A L
P O S I T I O N
N O T E : C E R T A I N B L O W E R P O S I T I O N S A R E N O T R E C O M M E N D E D .
FIGURE 1 - TYPICAL INDOOR UNIT
APPLICATIONS
The indoor units are built in a single cabinet with one conden-
sate drain pan. These units can be installed in either the verti-
cal or horizontal position for maximum flexibility.
NOTE: On vertical applications, the air velocity across the
indoor coil keeps the condensate from dripping off
the finned surface onto the filters.
NOTE: On horizontal applications the unit must be installed
with the condensate drain pan under the entire
indoor coil.
NOTE: The Supply Air Plenum and the Return Air Grille
accessories can be used on either arrangement.
NOTE: The Base accessory can only be used on the verti-
cal arrangement.
85
KW*
MBH
KW*
MBH
18.6
231
20.1
19.0
250
20.6
19.5
270
21.1
20.0
291
21.6
13.7
172
14.9
14.0
187
15.2
14.4
203
15.5
14.7
219
15.9
B L O W E R M O T O R
L O C A T I O N
R E T U R N A I R
D U C T F L A N G E
E V A P O R A T O R
F I L T E R S
C O I L
H O R I Z O N T A L
C O I L
P O S I T I O N
S E C T I O N
A L T E R N A T E A I R
D I S C H A R G E A R R A N G E M E N T S
B E C A U S E T H E B L O W E R M O T O R S H O U L D N O T B E M O U N T E D
U P S I D E D O W N .
95
105
KW*
MBH KW* MBH KW*
219
21.9
207 23.9 195 26.2
238
22.4
225 24.4 212 26.7
257
22.9
243 24.9 230 27.2
277
23.4
263 25.5 248 27.7
163
16.2
153 17.7 143 19.4
177
16.5
167 18.0 157 19.8
193
16.9
182 18.4 171 20.2
208
17.3
197 18.8 186 20.6
B L O W E R
S E C T I O N
115
3