Test/Disablements Menu - Bosch FPC-500-2 Operation Manual

Conventional fire panel
Hide thumbs Also See for FPC-500-2:
Table of Contents

Advertisement

20
en | Operation
Press the "Evacuation" key.
EVAC
ACK
RESET
EVAC button functions
The EVAC button has various functions, depending on the
status of the fire panel:
Silencing notification appliances
NOTICE!
Only silence an alarm once you have made sure that there is not
actually a fire.
You can reactivate silenced alarm devices using the EVAC
button.
Press the "Silence notification appliance" key.
The fire panel deactivates all notification appliances and
relays as programmed. A new alarm reactivates the
notification appliances and relays, if programmed.
4.2.2

Test/Disablements Menu

The following options are available in the test menu:
F.01U.172.982 | 5.0 | 2012.04
Press the ACK key.
The fire panel activates all notification appliances and
relays as programmed.
Press the "Reset" key.
No evacuation is triggered.
Panel in normal state
You can trigger a test alarm using the EVAC button.
Panel in alarm state
If you have silenced the notification appliances, you can
reactivate them using the EVAC button.
Panel in alarm verification, dual-zone dependency, or dual-
detector dependency state
The delay for the alarm notification appliances is ended.
The notification appliances are triggered immediately.
1-Test MMI
2-Test Zones
Operation Guide
Conventional Fire Panel
Bosch Sicherheitssysteme GmbH