Vertical Termination - Jøtul GF 300 DV II Allagash Installation And Operation Instructions Manual

Direct vent gas stove
Table of Contents

Advertisement

B
Figure 6. Exhaust restrictor positions - viewed from front
with top plate removed.
Vertical Vent Termination
The Jøtul GF 300 DV II can be vertically vented through a
ceiling or to a roof termination with the following guide-
lines:
The termination should fall within the shaded areas
of the grids depicted in the Vent Window diagrams on
pages 10 - 11.
run should not exceed 35 ft. (10.66 m).
Minimum Vertical run must be at least 8 ft. (2.43 m).
Maximum Colinear Horizontal run is 2 ft. (61 cm).
Vent Terminus Clearance: In no case shall any dis-
charge opening on the cap be less than 18 in. (610 mm)
horizontally from the roof surface.
Steep roofs, nearby trees, and predominantly windy
conditions can contribute to poor draft and/or pro-
mote down-draft occurances. Increasing the height of
the vent may alleviate these conditions.
Use Wall Straps to support an offset pipe run at
intervals of three feet to avoid excessive stress on the
offsets.
Elbows: Four 45°, or two 90° elbows may be used.
Do not include the 45° elbow attached to the stove.
Whenever possible use 45° elbows instead of 90°
elbows as they are less restrictive to exhaust gas and
intake air flow.
A firestop is required at every floor. The opening
should be framed to 10" X 10" inside dimension.
Any venting that is exposed above the first floor,
regardless of attic space or living space, must be en-
closed. Always maintain the required 1" clearance from
all sides of the vertical vent system.
D
C
A
See Fig. 6
Detail
Figure 7. Use a nut driver to change the Exhaust Restrictor
setting.
Horizontal Overhang
18”.
min.
Termination
Cap
Figure 8. Vertical vent termination height above roof.
137775_Rev_K 7.29.10
18”.
min.
Lowest Discharge
Opening
18” min.
9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents