Mitsubishi Electric MSZ-G09SV-E1 Service Manual page 47

Split-type, heat pump air conditioners wireless type
Hide thumbs Also See for MSZ-G09SV-E1:
Table of Contents

Advertisement

(Outdoor LED indication table)
MUZ-G09SV -
MUZ-G12SV -
E1
MUZ-G09SV -
MUZ-G12SV -
E2
NOTE 1. The location of LED is illustrated at the right figure.
2. LED lights up during normal operation.
No.
Symptom
LED indication
1-time flash every
Outdoor unit
2.5 seconds
1
does not
operate
2
NOTE:
For abnormality
location, refer to
3
'Indoor
troubleshooting
check table' on
4
page 41.
2-time flash
'Outdoor unit
5
2.5 seconds OFF
stops and
restarts 3
3-time flash
minutes later'
2.5 seconds OFF
6
is repeated
4-time flash
2.5 seconds OFF
7
5-time flash
2.5 seconds OFF
8
Outdoor unit
1-time flash
9
operates (at
2-5 seconds OFF
low
3-time flash
frequency)
2-5 seconds OFF
10
4-time flash
2-5 seconds OFF
11
Outdoor unit
5-time flash
operates
2-5 seconds OFF
12
6-time flash
13
2-5 seconds OFF
7-time flash
2-5 seconds OFF
14
The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the flashing frequency is "2".
ON
OFF
E1
E2
Abnormal point
Serial signal
When serial signal stops from indoor unit for 60 seconds,
compressor stops and then restarts 3 minutes later.
Outdoor power
When compressor has stopped by over current protection
system
within 1 minute after compressor start-up 3 times in a row,
compressor stops and then restarts 3 minutes later.
Outdoor
When discharge temperature thermistor or fin temperature
thermistors
thermistor shorts or opens during compressor running,
compressor stops and restarts 3 minutes later.
Outdoor control
When nonvolatile memory date cannot be read properly,
system
compressor stops and restarts 3 minutes later.
Over current
When 19A(MUZ-G09SV)/ 29A(MUZ-G12SV) current flows into
protection
power transistor, compressor stops and restarts 3 minutes later.
Discharge
When discharge temperature thermistor exceeds 116:,
temperature
compressor stops and restarts 3 minutes later.
overheat
(Compressor restarts when discharge temperature thermistor
protection
reads 100: or below.)
When temperature at heat sink exceeds 78:(MUZ-G09SV)/
Fin temperature
80:(MUZ-G12SV) or outdoor electronic control P.C. board
thermistor overheat
exceeds 68:(MUZ-G09SV)/ 78:(MUZ-G12SV), compressor
protection
stops and restarts 3 minutes later.
High pressure
When indoor coil thermistor exceeds 75:, compressor stops
protection
and restarts 3 minutes later.
Frequency drop by
When current from power outlet exceeds 8A(MUZ-G09SV)/
current protection
9A(MUZ-G12SV), compressor frequency lowers.
Frequency drop by
When indoor coil thermistor exceeds 55: in HEAT mode,
high pressure
compressor frequency lowers.
protection
Frequency drop by
When indoor coil thermistor reads 8: or below in COOL mode,
defrosting in COOL
compressor frequency lowers.
mode
Frequency drop by,
When discharge temperature thermistor exceeds 111:,
discharge
compressor frequency lowers.
temperature
protection.
When defrost thermistor short or open.
Outdoor
w In this case, compressor continues running.
thermistors.
Defrost thermistor.
Power factor
When power factor of compressor is not detected.
w In this case, compressor continues running.
detection
Low discharge
When discharge temperature has been 50: or below for 20
temperature
minutes.
protection
2.5-second OFF
Detection method
0.5-second ON
2.5-second OFF
47
<Outdoor electronic control P.C. board>
Transistor
Hybrid
module
IC
transformer
Checkpoint
· Refer to 'Checking serial signal
error' on page 48.
· Refer to M 'Check of power supply'
on page 56.
· Refer to A 'How to check inverter/
compressor' on page 51.
· Refer to J 'Check of outdoor
thermistors' on page 54.
Replace outdoor electronic control
P.C. board.
Refer to A 'How to check inverter/
compressor on page 51.
· Check refrigerant circuit and
refrigerant amount.
· Refer to J 'Check of outdoor
thermistors' on page 54.
· Check around outdoor unit.
· Check outdoor unit air passage.
· Check refrigerant circuit and
refrigerant amount.
· Check stop valve.
The unit is normal, but check the
following.
· Check if indoor filters are clogged
· Check if refrigerant is short.
· Check if indoor/outdoor unit air
outlets are short cycled.
Refer to J 'Check of outdoor
thermistors' on page 54.
Check compressor wiring.
· Refer to P 'Check of LEV' on
page 57.
· Check refrigerant circuit and
refrigerant amount.
0.5-second ON
LED
flashing