clearances

clearances to coMBustIBles
Follow these instructions carefully to ensure safe installation. Failure
to follow instructions exactly can create a fire hazard.
the appliance cannot be installed on a carpet, tile or other
combustible material other than wood flooring. If installed on carpet
or vinyl flooring, the appliance shall be installed on a metal, wood
or noncombustible material panel extending full width and depth of
the appliance.
Mantel clearances
note: The combustible area above the facing must not
protrude more than 3/4" from the facing. If it does, it is
considered a mantel and must meet the mantel requirements
listed in this manual.
never obstruct or modify the air inlet or outlet grills (louvers). this
may create a fire hazard.
FInIshInG MaterIal
note: Any remote wiring (i.e. remote control, wall switch, and optional fan) must be done prior to
final finishing to avoid costly reconstruction.
Only noncombustible materials (i.e. brick, tile, slate, steel, or other materials with a UL fire rating
of Zero) may be used to cover the black-painted face of the appliance. A 300°F minimum adhesive
may be used to attach facing materials to the black surface. If joints between the finished wall and
the fireplace surround are sealed, a 300°F minimum sealant material (General Electric RTV103 or
equivalent) must be used. Combustibles may come to the top and side edges but not overlay the
face.
42D0200
10"
12"
Top of Louvers
Figure 8 -
Mantel Clearances
FP2279
mantel clearance
2/09
6000DV Gas Fireplace
Wall
8"
Insulation Board
6"
4"
10"
2"
8"
6"
4"
FP2279
Standoff
13