Monessen Hearth 6000DV Installation And Operating Instructions Manual page 27

Direct vent gas fireplace
Table of Contents

Advertisement

vent InstallatIon
4. Connect a section of pipe and extend up through the hole.
note: If an offset is needed to avoid obstructions, you must support the vent pipe every three
(3) feet. use wall straps for this purpose. refer to Page 25, Figure 29. whenever possible, use
45° elbows instead of 90° elbows. the 45° elbow offers less restriction to the flow of the flue
gases and intake air.
5. Place the flashing over the pipe section(s) extending through the roof. Secure the base of the flash-
ing to the roof and framing with roofing nails. Be sure roofing material overlaps the top edge of the
flashing. There must be a 1" clearance from the vent pipe to combustible materials.
6. Continue to add pipe sections until the height of the vent cap meets the minimum building code
requirements.
note: you must increase vent height for steep roof pitches. nearby trees, adjoining roof lines,
steep pitched roofs, and other similar factors may cause poor draft or down-drafting in high
winds. Increasing the vent height may solve this problem.
note: If the vent pipe passes through any occupied areas above the first floor, including
storage spaces and closets, you must enclose pipe. you may frame and sheetrock the enclosure
with standard construction material. Make sure to meet the minimum allowable clearances to
combustibles. do not fill any of the required clearance spaces with insulation.
42D0200
6000DV Gas Fireplace
27