vent InstallatIon
horizontal sections of this vent system
require a minimum of 3" clearances to
combustibles at the top of the flue and
1" clearance at the sides and bottom
until the flue penetrates the outside
wall. a minimum 1" clearance all around
the flue is acceptable at this point of
penetration.
vertical sections of this vent system
require a minimum of 1" clearance to
combustibles on all sides of the pipe.
42D0200
this fireplace must be vented to the
outside. the venting system must never
be attached to a chimney serving a
separate solid fuel burning appliance.
each gas appliance must use a separate
vent system. do not use common vent
systems.
1 "
1 "
3 "
1 "
FP2280
Figure 9 -
Combustible Clearances for Vent Pipe
FP2280
vent pipe clear
6000DV Gas Fireplace
A Minimum of 3" Clearance to the Top Is
Required Along Horizontal Length until Flue
Pipe Penetrates Outside Wall.
A Minimum 1" Clearance to
Combustibles Permitted All
Around Flue at Outside Wall
15