Accel/Decel Time Setting - YASKAWA Varispeed-606PC3 Instruction Manual

Ultra-compact all-digital low-noise inverter
Table of Contents

Advertisement

P. DIGITAL OPERATOR (JVOP-114) (Confd)
ACCEL/DECEL TIME SETTING
0
-w
Each item can be set from 0,.0 sec to 600 sec .
00
The set time indicates the interval required before the ~-
maximum output frequency setting
M
is reached.
Accel/decel time can be set for two-step switching
using multifunction contact input, even during
running.
Between control circuit terminals 0) -
Open : F9 _
1
and F0 are selected.
Closed : 11 and 12 are selected.
(when setting F3_21 = 6)
OUTPUT
FREQUENCY
I ~ I
L__ 1
E 9 " I
11
Note : S-curve accel/decel reducing shock at motor starting is also
enabled. When S-curve accel/decel is needed, refer to "S-CURVE
PATTERN SELECTION" on page 100.
Item Name
Constant to be Set
Factory Preset
Acceleration Time 1
E91
10 .0s
Deceleration Time 1
~0
110 .0s
Acceleration Time 2
>>
110.0s
Deceleration Time 2
12
10.O s
Accel/Decel Time Select
I
0,
33, ®
See page 90.