Section 6: Mobile Home - Quadra-Fire YOSEMITE-MBK Owner's Manual

Yosemite series non-catalytic, front/side load, wood heater installation and operation
Hide thumbs Also See for YOSEMITE-MBK:
Table of Contents

Advertisement

Yosemite Wood Stove
D. Chimney Termination Requirements
Follow manufacturer's instructions for clearance, securing
flashing and terminating the chimney.
Must have an approved and Listed cap
Must not be located where it will become plugged
by snow or other material
Must terminate at least 3 feet (91cm) above the
roof and at least 2 feet (61cm) above any portion
of the roof within 10 feet (305cm).
Must be located away from trees or other struc-
tures
E. 2-10-3 Rule
These are safety requirements and are not meant to assure proper flue draft.
2 ft. (61cm)
10 ft. (305cm) To Nearest Roofline
3 ft. (91cm)
Minimum
Figure 20.1
10 ft. (305cm) or more
Wall or Parapet
3 ft. (91cm) Minimum
Figure 20.2
Page 20
NOTE:
Chimney performance may vary.
Trees, buildings, roof lines and wind conditions affect
performance.
Chimney height may need adjustment if smoking or
overdraft occurs.
Less than 10 ft. (305cm)
2 ft. (61cm)
3 ft. (91cm)
Minimum
Pitched Roof
Less than 10 ft. (305cm)
2 ft. (61cm)Minimum
3 ft. (91cm) Minimum
Flat Roof
7004-187H
R
6
Mobile Home Installation
You must use a Quadra-Fire Outside Air Kit Part
831-1780 for installation in a mobile home.
1. An outside air inlet must be provided for combustion See
page 15 for installation information.
2. Appliance must be secured to the mobile home structure
by bolting the pedestal through hearth pad and into floor.
3. Appliance must be grounded with #8 solid copper
grounding wire or equivalent and terminated at each end
with N.E.C. approved grounding device.
4. Appliance must be installed with an approved UL103 HT
ventilated chimney connector, UL103 HT chimney, and
terminal cap with spark arrestor. Never use a single wall
connector (stove pipe) in a mobile home installation. Use
only double-wall connector pipe, Dura-Vent DVL, Selkirk
metalbestos DS or Security DL double-wall connector or
any listed double-wall connector pipe.
5. In Canada, this appliance must be connected to a 6 inch
(152mm) factory-built chimney conforming to CAN/ULC-
629M, STANDARD FOR FACTORY BUILT CHIMNEYS.
6. Follow the chimney and chimney connector manufacturer's
instructions when installing the flue system for use in a
mobile home.
7. Maintain clearance to combustibles.
8. Floor protection requirements must be followed precisely.
9. Use silicone to create an effective vapor barrier at
the location where the chimney or other component
penetrates to the exterior of the structure.
NOTE: Offsets from the vertical, not exceeding 45°, are
allowed per Section 905(a) of the Uniform Mechanical Code
(UMC). Offsets greater than 45° are considered horizontal
and are also allowed, providing the horizontal run does not
exceed 75% of the vertical height of the vent. Construction,
clearance and termination must be in compliance with the
UMC Table 9C. This installation must also comply with NFPA
211.
NOTE: Top sections of chimney must be removable to allow
maximum clearance of 13.5 feet (411cm) from ground level
for transportation purposes.
10. Burn wood only. Other types of fuels may generate
poisonous gases (e.g., carbon monoxide).
11. If unit burns poorly while an exhaust blower is on in
home, (i.e., range hood), increase combustion air.
12. Installation shall be in accordance with the Manufacturers
Home & Safety Standard (HUD) CFR 3280, Part 24.
June 23, 2011
June 23, 2011
R
Storm Collar
Joist Shield &
Floor
Protector
Outside Air Floor Vent
Figure 21.1
THE STRUCTURAL INTEGRITY OF THE MOBILE HOME
FLOOR, WALL AND CEILING/ROOF MUST BE MAIN-
TAINED
Do NOT cut through:
• Floor joist, wall, studs or ceiling trusses.
• Any supporting material that would affect the structural
integrity.
Asphyxiation Risk.
NEVER INSTALL IN A SLEEPING ROOM.
Consumes oxygen in the room.
7004-187H
Yosemite Wood Stove
Spark Arrestor
Cap
Roof Flashing
Listed Chimney
Firestop
Connector
Outside Air Kit
Connector
CAUTION
WARNING
Page 21