Flex Vent Installation - Vermont Castings VWDV70 Installation And Operating Instructions Manual

70" linear wideview direct vent gas fireplace
Table of Contents

Advertisement

VWDV70 Series Gas Fireplace
1. Flexible UL1777 listed venting may be used in any
venting application where rigid direct vent components
can be used. all restrictions, clearances and allow-
ances that pertain to the rigid piping apply to the
flexible venting. Flex kits may not be modified. Flex
kits may be added to the end of a vent run made of rigid
vent sections using pipe manufacturer's approved flex
to pipe adapters. This may occur only if doing so does
not violate any of the venting length, height, routing,
horizontal to vertical ratio requirements or clearance
considerations detailed in this manual.
2. The flex adapter starter kit (DVFF8A/8) is used to attach
flex venting to the appliance starting collar. It includes
5" inner and 8" outer adapter rings. Figure 30
The inner and outer adapter rings are required to
start all flex runs.
Never install damaged or torn flexible venting.
Over tightening clamps may rip, tear, or otherwise
damage flexible venting.
The adapter kit does not include individual pipe sec-
tions which may be purchased separately. (UL1777
listed type venting only.)
3. Start the flexible vent as follows:
A. Installing the inner flex adapter and pipe. Figure
30
1. Insert the long side of the 5" inner ring into
exhaust pipe, gently tap to seat into place, and
secure with screws.
2. Slide the small gear clamp over the inner flexible
vent pipe, and push out of the way.
3. Pull and extend the inner flexible vent.
4. Slide the inner vent onto the adapter collar, for a
minimum 1
" overlap.
C\v
5. Locate the clamp at approximately 3/4" from the
flex end and tighten.
6. Secure the clamped inner section with three self-
tapping screws, drilled equidistant, just above the
clamp perimeter.
B. Installing the outer flex pipe. Figure 30
1. Firmly insert the 8" outer adapter ring into the
outer appliance starting collar and secure with
screws.
2. Slide the large gear clamp over the outer flexible
vent pipe, and push out of the way.
3. Pull and extend the outer flexible vent.
4. Slide the outer vent onto the appliance collar outer
adapter for a minimum 1
F l e x v e n t p i p e s p a c e r s : r e f e r t o
manufacturer's specifications for correct
positioning of the spacer springs to maintain
proper distance between inside and outside
pipe.
22
" overlap.
C\v

FLex Vent InstaLLatIon

1C\v" Flex-
ible Pipe
and Adapter
Outer
DVFF8A/8
Inner Adapter
Outer Adapter
Figure 30 -
Typical Appliance Connection
FP1972
5. Locate the clamp at approximately 3/4" from the
flex end and tighten.
appliance connection
6. Secure the clamped outer section with three self-
tapping screws, drilled equidistant, just above the
clamp perimeter.
C. Routing UL1777 flex pipe.
1. Always maintain the required clearance when
routing the flex vent assembly.
2. Install firestop spacers, Figure 32, when penetrat-
ing ceiling, attic spaces, or walls.
3. Do not allow the flexible vent to bend in radius
tighter than 5°. Figure 31
UL1777
Flex Vent
Figure 31 -
Minimum Radius for Flex
FP1973
Vent Section
flex pipe bend
UL1777
Flex Vent
equidistant just
Appliance
Starting Collar
5° Radius
FP1973
20303735
Screws
(3 places,
above gear
clamp)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents