Toshiba RAV-SM406BT-E Service Manual page 87

Split type
Hide thumbs Also See for RAV-SM406BT-E:
Table of Contents

Advertisement

No.
Part name
Drain pan
Drain pump
Float switch
Procedure
1. Detachment
1) Remove the drain cap and then extract the
drain water accumulated in the drain pan.
NOTE
When removing the drain cap, be sure to
receive drain water using a bucket, etc.
2) Loosen screws which fix the bottom base. (3
positions)
(For 140 type models, remove 2 screws at the
center.)
3) As shown in the right figure, when sliding it
toward arrow direction, the electric parts
cover the bottom base opens using the hinge
part as a shaft.
4) Hold handle of the drain pan and then pull off
slowly.
CAUTION
When removing the drain pan, do not hold the
drain socket. (Water leakage may be caused.)
2. Attachment
1) First hook the thin side of the drain pan to the
discharge panel and then push in the thick side.
2) Close the bottom base and fix it with screws.
1. Detachment
1) Perform works until opening of the electric
parts box cover in works of 1 of
2) Remove the connectors which connect to
float switch of the drain pump from the control
P.C. board.
CN34 : Float switch (3P, Red)
CN504 : Drain pump (2P, White)
3) Remove the fixing screws (2 positions) of the
check cover and then take out the check cover.
(To the check cover, the drain pump and float
switch are attached.)
4) Pick up the hose band, shift from the pump
connecting part, remove the drain hose and
then remove the check cover.
5) Remove screws which fix the drain pump
assembly and then remove the drain pump
assembly. (Ø4 x 10, 3 pcs.)
6) Remove the resin nut switch and then remove the
float switch from the fixing plate.
2. Attachment
1) Using the removed screws, fix the drain pump
assembly as original.
2) Using the removed resin nut, fix the float
switch as original.
3) Connect the drain hose as original and then
attach the hose band.
4) Connect the drain pump and the float switch
wiring as original and close the electric parts
box cover for fixing.
Be sure to perform wiring in the electric parts
box as original.
5) Enter the corners (2 positions) of the check
cover in the entering part and then fix it using
fixing screws (2 positions).
Discharge port
panel
.
Connector
position
CN34
CN504
Fixing screws
Fixing screws
Check cover
– 87 –
Remarks
Bottom base
Do not hold the
drain socket.
Screws
Drain socket
Drain socket
Drain pan
Entering part
Resin nut
Float switch
Float switch
Drain pump
Drain pump
Hose band
NG
NG
Handle
Screws

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents