Toshiba RAV-SM406BT-E Service Manual page 62

Split type
Hide thumbs Also See for RAV-SM406BT-E:
Table of Contents

Advertisement

DN
01
Filter sign lighting time
02
Filter pollution level
03
Central control address
06
Heating suction temperature shift
0F
Cooling only
10
Type
11
Indoor unit capacity
12
System address
13
Indoor unit address
14
Group address
Temperature range of cooling/heating
1E
automatic SW control point
28
Auto restart after power failure
2b
Thermo output SW (T10
31
Ventilation fan (standalone)
32
Sensor select (Selection of static pressure)
40
Drain pump control
5d
High ceiling SW (External static pressure selection)
60
Timer setting (wired remote controller)
8b
Correction of high heat feeling
C2
DEMAND setup
d0
Remote controller save function
d1
Frost protection function
d3
Revolutions per minute of dry operation
Table 2. Type: CODE No. 10
Setting data
0001∗
4-way Air Discharge Cassette Type
1
0004∗
Concealed Duce standard type
2
∗ 1 EEPROM initial value on the P. C. board for indoor unit servicing.
∗ 2
CAUTION
< Model Name : RAV-SM∗∗∗
For the above models, set the CODE No. to "
(intial) to "0001".
Item
)
Type
∗∗∗BT-E(TR)>
∗∗∗
∗∗∗
∗∗∗
" and the setting data 0000
CE
Table 1
Setting data
Type name abb.
RAV-SM∗∗∗BT-E (TR)
– 62 –
Factory-set value
Depending on Type
0000: standard
0099: Not determined
0002: +2°C
0000: Heat pump
Depending on model type
Depending on capacity type
0099: Not determined
0099: Not determined
0099: Not determined
0003: 3 deg (Ts ± 1.5)
0000: None
0000: Thermo ON
0000: Not available
0000: Body sensor
0003: Drain pump OFF
Depending on capacity type
0000: Available
0000: None
0075: 75%
0001: Valid
0000: Not available
0011: 310rpm
Table 3. Indoor unit capacity:
CODE No. 11
Setting data
0000∗
0006
0007
0009
0012
0015
0017
0018
∗ EEPROM initial value on the P.C.
board for indoor unit servicing.
Type
Disable
40
45
56
80
110
140
160