Exterior Factory-Built Chimney; Wall Penetrations Under 84 - Lopi Cape Cod Wood Stove Owner's Manual

Cape cod wood stove
Table of Contents

Advertisement

Stove Installation

Exterior Factory-Built Chimney

A vertical rise of 84" of chimney connector is required, measured from the floor, before entering a Class
'A' wall penetration. For those wishing to pass the chimney through the lower wall, a NFPA 211 wall
pass-through may be used (if approved by local building codes).

Wall Penetrations Under 84"

In cases where the chimney connector must be passed through a combustible wall or partition under 84",
the following NFPA 211 method may be used if local building codes permit. Check with local authorities
before installation to insure all necessary requirements have been met. Figure 12 details a wall pass-
through based on the NFPA 211 standard. After the pass-through, Class A Chimney may be used in
accordance with the chimney installation instructions.
© Travis Industries
(for qualified installers only)
NFPA 211 Wall Pass-Through
(see NFPA 211 for a full description)
Brick
Fire Clay Thimble
Combustible Materials
100-01383
12 Min.
12 Min.
15
Figure 9
4140402