Jøtul GF 400 DV Sebago Installation And Operation Instructions Manual page 11

Direct vent gas stove
Table of Contents

Advertisement

Vent Termination Zones - Propane
35 Ft.
(10.67 m)
30 Ft.
(9.14 m)
25 Ft.
(7.62 m)
A
20 Ft.
B
(6.10 m)
15 Ft.
(4.57 m)
12 Ft.
(3.65 m)
B
8 Ft.
(2.43 m)
5 Ft.
(1.52 m)
OPEN AIR INLET
RESTRICTOR
Min. Rise
2 Ft.
(.60 m)
5 Ft.
(1.52 m)
• VENTING MUST TERMINATE (END) WITHIN ONE OF THE DESIG-
NATED AREAS. ZONE "A" IS FOR VERTICAL TEMINATIONS ONLY.
• SET STOVE EXHAUST RESTRICTOR TO THE POSITION THAT CORRE-
SPONDS TO THE VENT TERMINATION AREA IN THE DIAGRAM
ABOVE.
• OPEN AIR INLET RESTRICTOR FOR TERMINATIONS 5 FT AND UNDER.
SEE FIG. 6, PAGE 9.
• ALWAYS MAINTAIN THE PROPER CLEARANCES TO COMBUSTIBLES.
The circled letter designations in the vent diagram correspond
to the Exhaust Restrictor Setting on the stove. First, determine
which vent termination zone is appropriate for your installation
and fuel type, then adjust the stove restrictor plate to the
corresponding position as shown in Figure 7, page 9.
Figure 11. Coaxial Vent Termination Window / LP
Horizontal and Vertical
Terminations for COAXIAL VENT
Up to four 45° or
two 90° elbows
permitted in
addition to the
starter elbow.
D
10 Ft.
15 Ft.
(3.05 m)
(4.57 m)
HORIZONTAL RUN
27 Ft.
20 Ft.
(8.22m)
(6.09 m)
Vertical
Termination for
COLINEAR VENT
35 Ft.
(10.67 m)
25 Ft.
(7.62 m)
C
D
Minimum
Minimum
Vertical
Vertical
Termination
Termination
8 Ft.
8 Ft.
(2.43 m)
(2.43 m)
2 Ft.
2 Ft.
(16 cm)
(16 cm)
• VENTING MUST
TERMINATE (END)
WITHIN THE SHADED
AREA.
• Adjust the Exhaust
Restrictor to position C
for a straight vertical
colinear termination.
• Adjust the Exhaust
Restrictor to position D
for a vertical colinear
termination with
maximum 2 ft. offset.
Figure 12 . Colinear Termination / LP
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents